Section 8: Compartmentation/sprinklers Openings in compartmentation

Openings in compartmentation

Openings in compartment walls separating buildings or occupancies

8.30

Openings in a compartment wall common to two or more buildings, or between different occupancies in the same building, should be limited to those for either of the following.

a. A fire doorset providing a means of escape, which has the same fire resistance as the wall and is fitted in accordance with the provisions in Appendix C.
b. The passage of a pipe that complies with the provisions in Section 10.

Openings in other compartment walls or in compartment floors

8.31

Openings should be limited to those for any of the following.

a. Fire doorsets fitted in accordance with the provisions in Appendix C.
b. Pipes, ventilation ducts, service cables, chimneys, appliance ventilation ducts or ducts encasing one or more flue pipes, complying with the provisions in Section 10.
c. Refuse chutes of class A1 construction.
d. Atria designed in accordance with Annexes B and C of BS 9999.
e. Protected shafts that conform to the provisions in the following paragraphs.