Section 8: Compartmentation/sprinklers
Section 8: Compartmentation/sprinklers
Provision of compartmentation
All purpose groups
8.1
All of the following should be provided as compartment walls and compartment floors and should have, as a minimum, the fire resistance given in Appendix B, Table B1.
8.2
A wall common to two or more buildings should be a compartment wall.
8.3
Parts of a building occupied mainly for different purposes should be separated from one another by compartment walls and/or compartment floors. Compartmentation is not needed if one of the different purposes is ancillary to the other. See paragraphs 0.23 and 0.24.
8.4
Effective compartmentation relies on both of the following.
8.5
The lowest floor in a building does not need to be a compartment floor.
Protected shafts
8.6
Stairs and service shafts connecting compartments should be protected to restrict the spread of fire between the compartments. These are called protected shafts. Walls or floors surrounding a protected shaft are considered to be compartment walls or compartment floors.
Places of special fire hazard
8.7
Fire resisting construction enclosing these places should achieve minimum REI 30. These walls and floors are not compartment walls and compartment floors.
‘Residential (institutional)’ buildings including health care
8.8
All floors should be constructed as compartment floors.
8.9
Paragraphs 2.35 and 2.36 give guidance on the provisions for compartment walls in care homes that use progressive horizontal evacuation.
‘Residential (other)’ buildings
8.10
In ‘residential (other)’ (purpose group (2(b)) buildings, all floors should be compartment floors.
Non-residential buildings
8.11
In buildings in a non-residential purpose group (purpose groups 3 to 7), the following should be compartment walls and compartment floors.
8.12
In two storey ‘shop and commercial’ or ‘industrial’ buildings (purpose groups 4 or 6), where the use of the upper storey is ancillary to the use of the ground storey, the ground storey may be treated as a single storey building for fire compartmentation purposes where all of the following apply.
Every place of special fire hazard (see Appendix E) should be enclosed with fire resisting construction.
Buildings containing one or more atria
8.13
Detailed advice on atria in buildings is given in Annexes B and C of BS 9999. For the purposes of this document, BS 9999 applies only where the atrium breaches a compartment.
Diagram 8.1 Compartment floors: illustration of guidance in paragraph 8.11

Table 8.1 Maximum dimensions of building or compartment (non-residential buildings)
| Purpose group of building or part | Height of floor of top storey above ground level (m) | Maximum floor area of any one storey in the building or any one storey in a compartment (m2) | ||
|---|---|---|---|---|
| Single storey buildings | Multi-storey buildings | |||
| Office | No limit(1) | No limit | No limit | |
| Assembly and recreation, shop and commercial: | ||||
a. Shops – without sprinkler system | No limit(1) | 2000 | 2000 | |
| Shops – with sprinkler system(2) | No limit | No limit | 4000 | |
b. Elsewhere – without sprinkler system | No limit(1) | No limit | 2000 | |
| Elsewhere – with sprinkler system(2) | No limit | No limit | 4000 | |
| Industrial(3) | ||||
| Without sprinkler system(1) | Not more than 18 | No limit | 7000 | |
| More than 18 | N/A | 2000(4) | ||
| With sprinkler system(2) | Not more than 18 | No limit | 14,000 | |
| More than 18 | N/A | 4000(4) | ||
| Height of floor of top storey above ground level (m) | Maximum floor area (m2) | Maximum height (m)(5) | Maximum compartment volume (m3) | |
| Single storey buildings | Multi-storey buildings | |||
| Storage(3) and other non-residential: | ||||
a. Car park for light vehicles | No limit | No limit | No limit | No limit |
b. Any other building or part: | ||||
| Without sprinkler system(1) | Not more than 18 | 20,000 | 18 | 20,000 |
| More than 18 | N/A | N/A | 4000(4) | |
| With sprinkler system(2) | Not more than 18 | No limit | No limit | 40,000 |
| More than 18 | 8000(4) | |||
NOTES:
This table recommends that where the maximum size limitations placed on a building without a sprinkler system are exceeded, a sprinkler system in accordance with Appendix E should be provided.
Sprinklers
8.14
Buildings within the ‘office’, ‘shop and commercial’, ‘assembly and recreation’, ‘industrial’ and ‘storage and other non-residential’ (except car parks for light vehicles) purpose groups (purpose groups 3 to 7(a)) require sprinklers where there is a top storey above 30m. The sprinkler system should be provided in accordance with Appendix E.
Construction of compartment walls and compartment floors
General provisions
8.15
All compartment walls and compartment floors should achieve both of the following.
8.16
Timber beams, joists, purlins and rafters may be built into or carried through a masonry or concrete compartment wall if the openings for them are both of the following.
If trussed rafters bridge the wall, failure of the truss due to a fire in one compartment should not cause failure of the truss in another compartment.
8.17
Where services could provide a source of ignition, the risk of fire developing and spreading into adjacent compartments should be controlled.
Compartment walls between buildings
8.18
Adjoining buildings should only be separated by walls, not floors. Compartment walls common to two or more buildings should comply with both of the following.
Separated parts of buildings
8.19
Compartment walls forming a separated part of a building should run the full height of the building in a continuous vertical plane.
Separated parts can be assessed independently to determine the appropriate standard of fire resistance in each. The two separated parts can have different standards of fire resistance.
Other compartment walls
8.20
Compartment walls not described in paragraphs 8.18 and 8.19 should run the full height of the storey in which they are situated.
8.21
Compartment walls in a top storey beneath a roof should be continued through the roof space.
Junction of compartment wall or compartment floor with other walls
8.22
At the junction with another compartment wall or an external wall, the fire resistance of the compartmentation should be maintained. Fire-stopping that meets the provisions in paragraphs 10.24 to 10.29 should be provided.
8.23
At the junction of a compartment floor and an external wall with no fire resistance, the external wall should be restrained at floor level. The restraint should reduce movement of the wall away from the floor if exposed to fire.
8.24
Compartment walls should be able to accommodate deflection of the floor, when exposed to fire, by either of the following means.
Where compartment walls are located within the middle half of a floor between vertical supports, the deflection may be assumed to be 40mm unless a smaller value can be justified by assessment. Outside this area, the limit can be reduced linearly to zero at the supports.
For steel beams that do not have the required fire resistance, reference should be made to SCI Publication P288.
Junction of compartment wall with roof
8.25
A compartment wall should achieve both of the following.
8.26
To reduce the risk of fire spreading over the roof from one compartment to another, a 1500mm wide zone of the roof, either side of the wall, should have a covering classified as BROOF(t4), on a substrate or deck of a material rated class A2-s3, d2 or better, as set out in Diagram 8.2a.
Thermoplastic rooflights that, because of paragraph 14.7, are regarded as having a BROOF(t4) classification are not suitable for use in that zone.
8.27
Materials achieving class B-s3, d2 or worse used as a substrate to the roof covering and any timber tiling battens, fully bedded in mortar or other suitable material for the width of the wall (Diagram 8.2b), may extend over the compartment wall in buildings that are both of the following.
8.28
Double-skinned insulated roof sheeting should incorporate a band of material rated class A2-s3, d2 or better, a minimum of 300mm in width, centred over the wall.
8.29
As an alternative to the provisions of paragraph 8.26 or 8.27, the compartment wall may extend through the roof for a minimum of either of the following (see Diagram 8.2c).
Diagram 8.2 Junction of compartment wall with roof

Openings in compartmentation
Openings in compartment walls separating buildings or occupancies
8.30
Openings in a compartment wall common to two or more buildings, or between different occupancies in the same building, should be limited to those for either of the following.
Openings in other compartment walls or in compartment floors
8.31
Openings should be limited to those for any of the following.
Protected shafts
8.32
Any stair or other shaft passing directly from one compartment to another should be enclosed in a protected shaft. Protected shafts should be used for the following only, but may also include sanitary accommodation and washrooms.
Construction of protected shafts
8.33
The construction enclosing a protected shaft (Diagram 8.3) should do all of the following.
Diagram 8.3 Construction of protected shafts

Uninsulated glazed screens to protected shafts
8.34
An uninsulated glazed screen may be incorporated in the enclosure to a protected shaft between a stair and a lobby or corridor entered from the stair. The enclosure must conform to Diagram 8.4 and meet all of the following conditions.
8.35
Where the measures in Diagram 8.4 are not provided, then both of the following apply.
Diagram 8.4 Uninsulated glazed screen separating protected shaft from lobby or corridor

Pipes for oil or gas and ventilation ducts in protected shafts
8.36
A protected shaft containing a protected stairway and/or a lift should not also contain either of the following.
A pipe that is completely separated from a protected shaft by fire resisting construction is not considered to be contained within that shaft.
8.37
In a protected shaft, any pipe carrying natural gas or LPG should be both of the following.
Ventilation of protected shafts conveying gas
8.38
A protected shaft conveying piped flammable gas should be ventilated direct to the outside air, by ventilation openings at high and low level in the shaft.
Any extension of the storey floor into the protected shaft should not compromise the free movement of air throughout the entire length of the shaft.
Guidance on shafts conveying piped flammable gas, including the size of ventilation openings, is given in BS 8313.
Openings into protected shafts
8.39
The external wall of a protected shaft does not normally need to have fire resistance. Situations where there are provisions are given in paragraph 3.29 (external walls of protected stairways, which may also be protected shafts) and paragraph 17.2 (firefighting shafts).
Openings in other parts of the enclosure to a protected shaft should be limited to the following.