Section 8: Compartmentation/sprinklers

Section 8: Compartmentation/sprinklers

Provision of compartmentation

All purpose groups

8.1

All of the following should be provided as compartment walls and compartment floors and should have, as a minimum, the fire resistance given in Appendix B, Table B1.

8.2

A wall common to two or more buildings should be a compartment wall.

8.3

Parts of a building occupied mainly for different purposes should be separated from one another by compartment walls and/or compartment floors. Compartmentation is not needed if one of the different purposes is ancillary to the other. See paragraphs 0.23 and 0.24.

8.4

Effective compartmentation relies on both of the following.

a. Fire resistance should be continuous at the join between elements forming a compartment.
b. Any openings between two compartments should not reduce the fire resistance.

8.5

The lowest floor in a building does not need to be a compartment floor.

Protected shafts

8.6

Stairs and service shafts connecting compartments should be protected to restrict the spread of fire between the compartments. These are called protected shafts. Walls or floors surrounding a protected shaft are considered to be compartment walls or compartment floors.

Places of special fire hazard

8.7

Fire resisting construction enclosing these places should achieve minimum REI 30. These walls and floors are not compartment walls and compartment floors.

‘Residential (institutional)’ buildings including health care

8.8

All floors should be constructed as compartment floors.

8.9

Paragraphs 2.35 and 2.36 give guidance on the provisions for compartment walls in care homes that use progressive horizontal evacuation.

‘Residential (other)’ buildings

8.10

In ‘residential (other)’ (purpose group (2(b)) buildings, all floors should be compartment floors.

Non-residential buildings

8.11

In buildings in a non-residential purpose group (purpose groups 3 to 7), the following should be compartment walls and compartment floors.

a. Every wall needed to divide the building to observe the compartment size limits in Table 8.1 (Diagram 8.1a).
b. Every floor, if the building or separated part of the building (see paragraph 8.19) has a top storey that is more than 30m above ground level (Diagram 8.1b).
c. The floor of the ground storey, if the building has one or more basements (Diagram 8.1c), except in small premises (see paragraph 4.2).
d. The floor of every basement storey (except the lowest floor), if the building or separated part has a basement more than 10m below ground level (Diagram 8.1d).
e. If the building comprises ‘shop and commercial’, ‘industrial’ or ‘storage’ premises (purpose groups 4, 6, 7): every wall or floor dividing a building into separate occupancies (spaces used by different organisations, whether they fall within the same purpose group or not).
f. See also the provision in paragraph 5.46 for store rooms in shops to be separated from retail areas by fire resisting construction (minimum REI 30).

8.12

In two storey ‘shop and commercial’ or ‘industrial’ buildings (purpose groups 4 or 6), where the use of the upper storey is ancillary to the use of the ground storey, the ground storey may be treated as a single storey building for fire compartmentation purposes where all of the following apply.

a. The area of the upper storey does not exceed the lower of:
i. 20% of the area of the ground storey
ii. 500m2.
b. The upper storey is compartmented from the lower one.
c. The upper storey has a means of escape independent of the lower storey escape routes.

Every place of special fire hazard (see Appendix E) should be enclosed with fire resisting construction.

Buildings containing one or more atria

8.13

Detailed advice on atria in buildings is given in Annexes B and C of BS 9999. For the purposes of this document, BS 9999 applies only where the atrium breaches a compartment.

Diagram 8.1 Compartment floors: illustration of guidance in paragraph 8.11

Diagram 8.1 Compartment floors: illustration of guidance in paragraph 8.11. Wording on the drawing: See para 8.11; b. Compartmentation in buildings over 30m see paragraph 8.11b Compartment floor(s) or wall(s); a. Example of compartmentation in an unsprinklered assembly and recreation, shop, or commercial building see paragraph 8.11a; > 30m; Storey not exceeding; 2000m²; Storey not exceeding; Roof; 2000m²; 30m max.; Storey exceeding 2000m² divided by compartment wall; Compartment; wall; Storey exceeding 2000m² divided by compartment wall; Compartment; wall; None of the floors in this case would need to be compartment floors, but the two storeys exceeding 2000m² would need to be divided into compartments not more than 2000m² by compartment walls.; In a building with a top storey over 30m in height all storeys should be separated by compartment floors. For advice on the special conditions in atrium buildings see Annex B of BS 9999.; The compartment walls in example (a) do not need to be in one vertical plane.; d. Deep basement see paragraph 8.11d; c. Shallow basement see paragraph 8.11c; > 10m; 10m max.; Only the floor of the ground storey need be a compartment floor if the lower basement is at a depth of not more than 10m.; All basement storeys to be separated by compartment floors if any storey is at a depth of more than 10m.
Diagram 8.1 Compartment floors: illustration of guidance in paragraph 8.11

Table 8.1 Maximum dimensions of building or compartment (non-residential buildings)

Purpose group of building or partHeight of floor of top storey above ground level (m)Maximum floor area of any one storey in the building or any one storey in a compartment (m2)
Single storey buildingsMulti-storey buildings
OfficeNo limit(1) No limitNo limit
Assembly and recreation, shop and commercial:
a. Shops – without sprinkler system
No limit(1) 20002000
Shops – with sprinkler system(2) No limitNo limit4000
b. Elsewhere – without sprinkler system
No limit(1) No limit2000
Elsewhere – with sprinkler system(2) No limitNo limit4000
Industrial(3)
Without sprinkler system(1) Not more than 18No limit7000
More than 18N/A2000(4)
With sprinkler system(2) Not more than 18No limit14,000
More than 18N/A4000(4)
Height of floor of top storey above ground level (m)Maximum floor area (m2)Maximum height (m)(5) Maximum compartment volume (m3)
Single storey buildingsMulti-storey buildings
Storage(3) and other non-residential:
a. Car park for light vehicles
No limitNo limitNo limitNo limit
b. Any other building or part:
Without sprinkler system(1) Not more than 1820,0001820,000
More than 18N/AN/A4000(4)
With sprinkler system(2) Not more than 18No limitNo limit40,000
More than 188000(4)

NOTES:

This table recommends that where the maximum size limitations placed on a building without a sprinkler system are exceeded, a sprinkler system in accordance with Appendix E should be provided.

1. See Appendix B, Table B2 for sprinkler system height requirements.
2. ‘With sprinkler system’ means that the building is fitted throughout with an automatic sprinkler system in accordance with Appendix E.
3. In certain industrial and storage uses that are subject to other legislation, for example the storage of LPG and certain chemicals, additional limitations on floor area and/or additional sprinkler provisions might apply.
4. This reduced limit applies only to storeys that are a minimum of 18m above ground level. Below this height the higher limit applies.
5. Compartment height is measured from finished floor level to the underside of the roof or ceiling.

Sprinklers

8.14

Buildings within the ‘office’, ‘shop and commercial’, ‘assembly and recreation’, ‘industrial’ and ‘storage and other non-residential’ (except car parks for light vehicles) purpose groups (purpose groups 3 to 7(a)) require sprinklers where there is a top storey above 30m. The sprinkler system should be provided in accordance with Appendix E.

Construction of compartment walls and compartment floors

General provisions

8.15

All compartment walls and compartment floors should achieve both of the following.

a. Form a complete barrier to fire between the compartments they separate.
b. Have the appropriate fire resistance, as given in Appendix B, Table B1 and Table B2.

8.16

Timber beams, joists, purlins and rafters may be built into or carried through a masonry or concrete compartment wall if the openings for them are both of the following.

a. As small as practicable.
b. Fire-stopped.

If trussed rafters bridge the wall, failure of the truss due to a fire in one compartment should not cause failure of the truss in another compartment.

8.17

Where services could provide a source of ignition, the risk of fire developing and spreading into adjacent compartments should be controlled.

Compartment walls between buildings

8.18

Adjoining buildings should only be separated by walls, not floors. Compartment walls common to two or more buildings should comply with both of the following.

a. Run the full height of the building in a continuous vertical plane.
b. Be continued through any roof space to the underside of the roof.

Separated parts of buildings

8.19

Compartment walls forming a separated part of a building should run the full height of the building in a continuous vertical plane.

Separated parts can be assessed independently to determine the appropriate standard of fire resistance in each. The two separated parts can have different standards of fire resistance.

Other compartment walls

8.20

Compartment walls not described in paragraphs 8.18 and 8.19 should run the full height of the storey in which they are situated.

8.21

Compartment walls in a top storey beneath a roof should be continued through the roof space.

Junction of compartment wall or compartment floor with other walls

8.22

At the junction with another compartment wall or an external wall, the fire resistance of the compartmentation should be maintained. Fire-stopping that meets the provisions in paragraphs 10.24 to 10.29 should be provided.

8.23

At the junction of a compartment floor and an external wall with no fire resistance, the external wall should be restrained at floor level. The restraint should reduce movement of the wall away from the floor if exposed to fire.

8.24

Compartment walls should be able to accommodate deflection of the floor, when exposed to fire, by either of the following means.

a. Between the wall and floor, provide a head detail that is capable of maintaining its integrity while deforming.
b. Design the wall so it maintains its integrity by resisting the additional vertical load from the floor above.

Where compartment walls are located within the middle half of a floor between vertical supports, the deflection may be assumed to be 40mm unless a smaller value can be justified by assessment. Outside this area, the limit can be reduced linearly to zero at the supports.

For steel beams that do not have the required fire resistance, reference should be made to SCI Publication P288.

Junction of compartment wall with roof

8.25

A compartment wall should achieve both of the following.

a. Meet the underside of the roof covering or deck, with fire-stopping to maintain the continuity of fire resistance.
b. Be continued across any eaves.

8.26

To reduce the risk of fire spreading over the roof from one compartment to another, a 1500mm wide zone of the roof, either side of the wall, should have a covering classified as BROOF(t4), on a substrate or deck of a material rated class A2-s3, d2 or better, as set out in Diagram 8.2a.

Thermoplastic rooflights that, because of paragraph 14.7, are regarded as having a BROOF(t4) classification are not suitable for use in that zone.

8.27

Materials achieving class B-s3, d2 or worse used as a substrate to the roof covering and any timber tiling battens, fully bedded in mortar or other suitable material for the width of the wall (Diagram 8.2b), may extend over the compartment wall in buildings that are both of the following.

a. A maximum of 15m high.
b. In one of the following purpose groups.
i. All residential purpose groups (purpose groups 1 and 2) other than ‘residential (institutional)’ (purpose group 2(a)).
ii. ‘Office’ (purpose group 3).
iii. ‘Assembly and recreation’ (purpose group 5).

8.28

Double-skinned insulated roof sheeting should incorporate a band of material rated class A2-s3, d2 or better, a minimum of 300mm in width, centred over the wall.

8.29

As an alternative to the provisions of paragraph 8.26 or 8.27, the compartment wall may extend through the roof for a minimum of either of the following (see Diagram 8.2c).

a. Where the height difference between the two roofs is less than 375mm, 375mm above the top surface of the adjoining roof covering.
b. 200mm above the top surface of the adjoining roof covering where either of the following applies.
i. The height difference between the two roofs is 375mm or more.
ii. The roof coverings either side of the wall are of a material classified as BROOF(t4).

Diagram 8.2 Junction of compartment wall with roof

Diagram 8.2 Junction of compartment wall with roof. Wording on the drawing: See paras 8.26 to 8.29; a. ANY BUILDING OR COMPARTMENT; Roof covering over this distance to be designated BROOF(t4) rated on deck of material of class A2-s3, d2 or better. Roof covering and deck could be composite structure, e.g. profiled steel cladding.; 1500mm 1500mm; Double-skinned insulated roof sheeting should incorporate a band of material rated class A2-s3, d2 or better, a minimum of 300mm in width, centred over the wall.; If roof support members pass through the wall, fire protection to these members for a distance of 1500mm on either side of the wall may be needed to delay distortion at the junction (see paragraph 8.16).; Wall; Fire-stopping to be carried up to underside of roof covering, e.g. roof tiles.; b. RESIDENTIAL (OTHER), OFFICE, OR ASSEMBLY AND RECREATION USE, AND NOT MORE THAN 15M HIGH; Roof covering to be designated BROOF(t4) rated for at least this distance.; Boarding (used as a substrate) or timber tiling battens may be carried over the wall provided that they are fully bedded in mortar (or other no less suitable material) where over the wall.; X; Thermoplastic insulation materials should not be carried over the wall.; 1500mm 1500mm; Double-skinned insulated roof sheeting with a thermoplastic core should incorporate a band of material of class A2-s3, d2 at least 300mm wide centred over the wall.; Sarking felt may also be carried over the wall.; If roof support members pass through the wall, fire protection to these members for a distance of 1500mm on either side of the wall may be needed to delay distortion at the junction (see paragraph 8.16).; Wall; Fire-stopping to be carried up to underside of roof covering, boarding or slab.; X; Section X–X; Roof covering to be designated BROOF(t4) rated for at least 1500mm either side of wall.; Roofing battens and sarking felt may be carried over the wall.; Fire-stopping to be carried up to underside of roof covering above and below sarking felt.; NOTES: 1. Fire-stopping should be carried over the full thickness of the wall. 2. Fire-stopping should be extended into any eaves. 3. The compartment wall does not necessarily need to be constructed of masonry.; c. ANY BUILDING OR COMPARTMENT; At least 375mm; The wall should be extended up through the roof for a height of at least 375mm above the top surface of the adjoining roof covering.; At least 375mm; Roof covering; Where there is a height di˜erence of at least 375 mm between two roofs or where the roof coverings on either side of the wall are BROOF(t4) rated, the height of the upstand/parapet wall above the highest roof may be reduced to 200mm.; Roof covering; Wall
Diagram 8.2 Junction of compartment wall with roof

Openings in compartmentation

Openings in compartment walls separating buildings or occupancies

8.30

Openings in a compartment wall common to two or more buildings, or between different occupancies in the same building, should be limited to those for either of the following.

a. A fire doorset providing a means of escape, which has the same fire resistance as the wall and is fitted in accordance with the provisions in Appendix C.
b. The passage of a pipe that complies with the provisions in Section 10.

Openings in other compartment walls or in compartment floors

8.31

Openings should be limited to those for any of the following.

a. Fire doorsets fitted in accordance with the provisions in Appendix C.
b. Pipes, ventilation ducts, service cables, chimneys, appliance ventilation ducts or ducts encasing one or more flue pipes, complying with the provisions in Section 10.
c. Refuse chutes of class A1 construction.
d. Atria designed in accordance with Annexes B and C of BS 9999.
e. Protected shafts that conform to the provisions in the following paragraphs.

Protected shafts

8.32

Any stair or other shaft passing directly from one compartment to another should be enclosed in a protected shaft. Protected shafts should be used for the following only, but may also include sanitary accommodation and washrooms.

a. Stairs.
b. Lifts.
c. Escalators.
d. Chutes.
e. Ducts.
f. Pipes.
g. Additional provisions apply for both of the following.
i. Protected shafts that are protected stairways: Sections 2 to 5.
ii. Stairs that are also firefighting stairs: Section 17.

Construction of protected shafts

8.33

The construction enclosing a protected shaft (Diagram 8.3) should do all of the following.

a. Form a complete barrier to fire between the compartments connected by the shaft.
b. Have the appropriate fire resistance given in Appendix B, Table B1, except for uninsulated glazed screens that meet the provisions of paragraph 8.34.
c. Satisfy the provisions for ventilation and the treatment of openings in paragraphs 8.38 and 8.39.

Diagram 8.3 Construction of protected shafts

Diagram 8.3 Construction of protected shafts. Wording on the drawing: See para 8.33; This diagram shows three common examples which illustrate the principles of the construction of protected shafts. The elements enclosing the shaft (unless formed by adjacent external walls) are compartment walls and floors.; Fd Fire doorset; Compartment wall; Fd Fd Fd Fd; External wall; A B C; Protected shaft A is bounded on three sides by compartment walls and on the fourth side by an external wall; Protected shaft C is a services duct bounded on four sides by compartment walls; Protected shaft B is bounded on four sides by compartment walls; The shaft structure (including any openings) should meet the relevant provisions for both of the following: compartment walls (see paragraphs 8.15 to 8.31) and external walls (see Sections 12 and 13 and Diagram 3.3).
Diagram 8.3 Construction of protected shafts

Uninsulated glazed screens to protected shafts

8.34

An uninsulated glazed screen may be incorporated in the enclosure to a protected shaft between a stair and a lobby or corridor entered from the stair. The enclosure must conform to Diagram 8.4 and meet all of the following conditions.

a. The standard of fire resistance required for the protected stairway is not more than REI 60.
b. The glazed screen complies with the following.
i. It achieves a minimum rating of E 30.
ii. It complies with the guidance on limits on areas of uninsulated glazing in Appendix B, Table B3.
c. The lobby or corridor is enclosed with fire resisting construction achieving a minimum rating of REI 30.

8.35

Where the measures in Diagram 8.4 are not provided, then both of the following apply.

a. The enclosing walls should comply with Appendix B, Table B1.
b. The doors should comply with Appendix B, Table B3.

Diagram 8.4 Uninsulated glazed screen separating protected shaft from lobby or corridor

Diagram 8.4 Uninsulated glazed screen separating protected shaft from lobby or corridor. Wording on the drawing: paras 8.34 and 8.35; a. With corridor b. With lobby; External wall; Fire resistance of protected shaft to be a maximum of REI 60; Protected shaft; Protected; shaft; Corridor Uninsulated glazed screen (minimum RE 30) Uninsulated glazed screen (minimum RE 30); Fire resistance of construction to be a minimum of REI 30; Fire resistance of glazed screen to be a minimum of RE 30; Protected; lobby; Fire doorsets that are a minimum of E 30 Sa
Diagram 8.4 Uninsulated glazed screen separating protected shaft from lobby or corridor

Pipes for oil or gas and ventilation ducts in protected shafts

8.36

A protected shaft containing a protected stairway and/or a lift should not also contain either of the following.

a. A pipe that conveys oil, other than in the mechanism of a hydraulic lift.
b. A ventilating duct. Two exceptions are as follows.
i. A duct provided for pressurising the protected stairway to keep it smoke free.
ii. A duct provided only to ventilate the protected stairway.

A pipe that is completely separated from a protected shaft by fire resisting construction is not considered to be contained within that shaft.

8.37

In a protected shaft, any pipe carrying natural gas or LPG should be both of the following.

a. Of screwed steel or all-welded steel construction.
b. Installed in accordance with both of the following.
i. The Pipelines Safety Regulations 1996.
ii. The Gas Safety (Installation and Use) Regulations 1998.

Ventilation of protected shafts conveying gas

8.38

A protected shaft conveying piped flammable gas should be ventilated direct to the outside air, by ventilation openings at high and low level in the shaft.

Any extension of the storey floor into the protected shaft should not compromise the free movement of air throughout the entire length of the shaft.

Guidance on shafts conveying piped flammable gas, including the size of ventilation openings, is given in BS 8313.

Openings into protected shafts

8.39

The external wall of a protected shaft does not normally need to have fire resistance. Situations where there are provisions are given in paragraph 3.29 (external walls of protected stairways, which may also be protected shafts) and paragraph 17.2 (firefighting shafts).

Openings in other parts of the enclosure to a protected shaft should be limited to the following.

a. If a wall common to two or more buildings forms part of the enclosure, only the following openings should be made in that wall.
i. A fire doorset providing a means of escape, which has the same fire resistance as the wall and is fitted in accordance with the provisions in Appendix C.
ii. The passage of a pipe that meets the provisions in Section 10.
b. Other parts of the enclosure (other than an external wall) should only have openings for any of the following.
i. Fire doorsets of the appropriate fire resistance, fitted in accordance with the provisions in Appendix C.
ii. The passage of pipes which meet the provisions in Section 10.
iii. Inlets to, outlets from and openings for a ventilation duct (if the shaft contains or serves as a ventilating duct), meeting the provisions in Section 10.
iv. The passage of lift cables into a lift machine room (if the shaft contains a lift). If the machine room is at the bottom of the shaft, the openings should be as small as practicable.