Section 5: General provisions Protection of escape routes
Protection of escape routes
Fire resistance of enclosures
5.2
Fire resistance test criteria are set out in Appendix B. Standards of performance are summarised in Table B1 and Table B2. Apart from specific situations described in Sections 1 and 2, and requirements B3 and B5, a minimum performance of REI 30 is sufficient to protect means of escape.
Fire resistance of doors
5.3
Fire resistance test criteria are set out in Appendix C. Standards of performance are summarised in Table C1.
Fire resistance of glazed elements
5.4
If glazed elements in fire resisting enclosures and doors can only meet the required integrity performance, their use is limited. These limitations depend on whether the enclosure forms part of a protected shaft (see Section 8) and the provisions set out in Appendix B, Table B3. If both integrity and insulation performance can be met, there is no restriction in this document on the use or amount of glass.
5.5
Glazed elements should also comply with the following, where necessary.