Section 3: Design for vertical escape Provision of refuges
Provision of refuges
3.4
Refuges form part of the management plan and offer relatively safe areas for people to wait for a short period only. Refuges should meet the following conditions.
3.5
The following are both examples of satisfactory refuges.
3.6
Refuges should be a minimum of 900mm × 1400mm in size and accessible by someone in a wheelchair. Where sited in a protected stairway, protected lobby or protected corridor, they should not reduce the width of the escape route or obstruct the flow of people escaping.
3.7
Refuges should be provided with an emergency voice communication (EVC) system complying with BS 5839-9. It should consist of Type B outstations communicating with a master station in the building control room (if one exists) or next to the fire detection and alarm panel. In some buildings, wireless technology may be more appropriate.
3.8
Refuges and evacuation lifts should be clearly identified. In protected lobbies and protected stairways there should be a blue mandatory sign worded ‘Refuge – keep clear’ in addition to fire safety signs.
3.9
Paragraph 5.32 gives guidance on using lifts, including evacuation lifts, during a fire.
Diagram 3.1 Refuge formed by compartmentation

Diagram 3.2 Refuge formed in a protected stairway