Section 5: General provisions Refuse chutes and storage
Refuse chutes and storage
5.42
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
5.43
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
a. Be separated from other parts of the building by fire resisting construction (minimum REI 30 in buildings with a top storey up to 5m above ground level; otherwise REI 60).
b. Not be situated within a protected stairway or protected lobby.
5.44
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
a. Be directly from the open air.
b. Be through a protected lobby with a minimum 0.2m2 of permanent ventilation.
5.45
Access openings to refuse storage chambers should not be sited next to escape routes or final exits.