Application of the fire resistance standards in Table B2 (2029 amendment) Table B3 Limitations on the use of uninsulated glazed elements on escape routes. These limitations do not apply to glazed elements that satisfy the relevant insulation criterion, see Table B1 (2029 amendment)

Table B3 Limitations on the use of uninsulated glazed elements on escape routes. These limitations do not apply to glazed elements that satisfy the relevant insulation criterion, see Table B1 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Table B3 Limitations on the use of uninsulated glazed elements on escape routes. These limitations do not apply to glazed elements that satisfy the relevant insulation criterion, see Table B1.

Position of glazed elementMaximum total glazed area in parts of a building with access to:
A single stairMore than one stair
WallsDoor leafWallsDoor leaf
Flats
1. Within the enclosures of a protected entrance hall or protected landing, or within fire resisting separation shown in Section 3, Diagram 3.4 of Approved Document B Volume 1.
Fixed fanlights onlyUnlimited above 1100mm from floorFixed fanlights onlyUnlimited above 1100mm from floor
Dwellinghouses
2. Within either:
a. the enclosures of a protected stairway
b. fire resisting separation shown in Diagram 2.2 of Approved Document B Volume 1.
Unlimited above 1100mm from floor or pitch of the stairUnlimitedUnlimited above 1100mm from floor or pitch of the stairUnlimited
3. Within fire resisting separation either:
a. shown in Diagram 2.4 of Approved Document B Volume 1
b. described in paragraph 2.16b of Approved Document B Volume 1.
Unlimited above 100mm from floorUnlimited above 100mm from floorUnlimited above 100mm from floorUnlimited above 100mm from floor
4. Existing window between an attached/ integral garage and the dwellinghouse.
UnlimitedNot applicableUnlimitedNot applicable
5. Adjacent to an external escape stair (see paragraph 2.17 and Diagram 2.7 of Approved Document B Volume 1) or roof escape route (see paragraph 2.13 of Approved Document B Volume 1).
UnlimitedUnlimitedUnlimitedUnlimited
General (except dwellinghouses)
6. Between residential/sleeping accommodation and a common escape route (corridor, lobby or stair).
NilNilNilNil
7. Between a protected stairway(1) and either:
a. the accommodation
b. a corridor that is not a protected corridor other than in item 6 above.
Nil25% of door areaUnlimited above 1100mm(2) 50% of door area
8. Between either:
a. a protected stairway(1) and a protected lobby or protected corridor
b. accommodation and a protected lobby other than in item 6 above.
Unlimited above 1100mm from floorUnlimited above 100mm from floorUnlimited above 100mm from floorUnlimited above 100mm from floor
9. Between the accommodation and a protected corridor that forms a dead end, other than in item 6 above.
Unlimited above 1100mm from floorUnlimited above 100mm from floorUnlimited above 1100mm from floorUnlimited above 100mm from floor
10. Between accommodation and any other corridor, or sub-dividing corridors, other than in item 6 above.
Not applicableNot applicableUnlimited above 100mm from floorUnlimited above 100mm from floor
11. Beside an external escape route.
Unlimited above 1100mm from floorUnlimited above 1100mm from floorUnlimited above 1100mm from floorUnlimited above 1100mm from floor
12. Beside an external escape stair (see paragraph 3.32 and Diagram 3.4) or roof escape route (see paragraph 2.32).
UnlimitedUnlimitedUnlimitedUnlimited

NOTES:

Items 1 and 8 apply also to single storey buildings.

Fire resisting glass should be marked with the name of the manufacturer and the name of the product.

Further guidance can be found in A Guide to Best Practice in the Specification and Use of Fire-resistant Glazed Systems published by the Glass and Glazing Federation.

1. If the protected stairway is also a protected shaft or a firefighting stair (see Section 17), there may be further restrictions on the use of glazed elements.
2. Measured vertically from the landing floor level or the stair pitch line.
3. The 100mm limit is intended to reduce the risk of fire spreading from a floor covering.