Section 4: Small premises Travel distance and number of escape routes
Travel distance and number of escape routes
4.6
Escape routes should be sited so that the travel distance from any point of a storey to the nearest storey exit does not exceed the distance given in Table 4.1 (see Diagrams 4.1, 4.2 and 4.3). The siting of two or more exits or stairs should give effective alternative directions of travel from any point in a storey.
Table 4.1 Maximum travel distances in small premises
| Storey | Maximum travel distance (m) |
|---|---|
| Ground storey with a single exit | 27 |
| Basement or first storey with a single stair | 18 |
| Storey with more than one exit/stair | 45 |
NOTES:
If the internal layout of partitions, fittings, etc. is not known, direct distances, rather than travel distances, should be assessed. The direct distance should be assumed to be two-thirds of the travel distance.
The travel distance in small premises with an open stair is measured as follows.
a. In a basement: to the foot of the stair.
b. On a first storey: to the head of the stair.
Diagram 4.1 Maximum travel distances in a small two or three storey premises with a single protected stairway to each storey

Diagram 4.2 Maximum travel distances in a small three storey premises with a single open stair

Diagram 4.3 Maximum travel distances in a small three storey premises with a single stair to each storey