Technical solution 5.9
5.9
A solid external wall in conditions of very severe exposure should be protected by external impervious cladding, but in conditions of severe exposure may be built as follows:
a. brickwork or stonework at least 328mm thick, dense aggregate concrete blockwork at least 250mm thick, or lightweight aggregate or aerated autoclaved concrete blockwork at least 215mm thick; and
b. rendering: the exposed face of the bricks or blocks should be rendered or be given no less protection. Rendering should be in two coats with a total thickness of at least 20mm and should have a scraped or textured finish. The strength of the mortar should be compatible with the strength of the bricks or blocks. The joints, if the wall is to be rendered, should be raked out to a depth of at least 10mm. Further guidance is given in BS EN 998:2003105. The rendering mix should be one part of cement, one part of lime and six parts of well graded sharp sand (nominal mix 1:1:6) unless the blocks are of dense concrete aggregate, in which case the mix may be 1:0.5:4. BS 5262:1991106 includes recommendations for a wider range of mixes according to the severity of exposure and the type of brick or block.
Premixed and proprietary renders should be used in accordance with the manufacturer’s instructions;
c. protection should be provided where the top of walls, etc. would otherwise be unprotected (see Diagram 10). Unless the protection and joints will be a complete barrier to moisture, a damp-proof course should also be provided;
d. damp-proof courses, cavity trays and closers should be provided and designed to ensure that water drains outwards:
i. where the downward flow will be interrupted by an obstruction, such as some types of lintel; and
ii. under openings, unless there is a sill and the sill and its joints will form a complete barrier; and
iii. at abutments between walls and roofs.