Section 5: Walls Solid external walls
Solid external walls
5.8
Any solid wall will meet the requirement if it will hold moisture arising from rain and snow until it can be released in a dry period without penetrating to the inside of the building, or causing damage to the building. The wall thickness will depend on the type of brick and block and on the severity of wind-driven rain. A method of describing the exposure to wind-driven rain is given in BS 8104:1992103; see also BS 5628-3:2001104.
Technical solution
5.9
A solid external wall in conditions of very severe exposure should be protected by external impervious cladding, but in conditions of severe exposure may be built as follows:
Premixed and proprietary renders should be used in accordance with the manufacturer’s instructions;
Diagram 10 Protection of wall head from precipitation (see paragraph 5.9(c))

5.10
Insulation. A solid external wall may be insulated on the inside or on the outside. Where it is on the inside a cavity should be provided to give a break in the path for moisture and where it is on the outside it should provide some resistance to the ingress of moisture to ensure the wall remains relatively dry (see Diagram 11).
103 BS 8104:1992 Code of practice for assessing exposure of walls to wind-driven rain.
104 BS 5628-3:2001 Code of practice for use of masonry. Materials and components, design and workmanship.
105 BS EN 998-2:2003 Specification for mortar for masonry. Masontry mortar.
106 BS 5262:1991 Code of practice for external renderings.
Alternative approach
5.11
The requirement can also be met by following the relevant recommendations of BS 5628-3:2001107. The code describes alternative constructions to suit the severity of the exposure and the type of brick or block.