Section 5: Walls Solid external walls

Solid external walls

5.8

Any solid wall will meet the requirement if it will hold moisture arising from rain and snow until it can be released in a dry period without penetrating to the inside of the building, or causing damage to the building. The wall thickness will depend on the type of brick and block and on the severity of wind-driven rain. A method of describing the exposure to wind-driven rain is given in BS 8104:1992103; see also BS 5628-3:2001104.

Technical solution

5.9

A solid external wall in conditions of very severe exposure should be protected by external impervious cladding, but in conditions of severe exposure may be built as follows:

a. brickwork or stonework at least 328mm thick, dense aggregate concrete blockwork at least 250mm thick, or lightweight aggregate or aerated autoclaved concrete blockwork at least 215mm thick; and
b. rendering: the exposed face of the bricks or blocks should be rendered or be given no less protection. Rendering should be in two coats with a total thickness of at least 20mm and should have a scraped or textured finish. The strength of the mortar should be compatible with the strength of the bricks or blocks. The joints, if the wall is to be rendered, should be raked out to a depth of at least 10mm. Further guidance is given in BS EN 998:2003105. The rendering mix should be one part of cement, one part of lime and six parts of well graded sharp sand (nominal mix 1:1:6) unless the blocks are of dense concrete aggregate, in which case the mix may be 1:0.5:4. BS 5262:1991106 includes recommendations for a wider range of mixes according to the severity of exposure and the type of brick or block.

Premixed and proprietary renders should be used in accordance with the manufacturer’s instructions;

c. protection should be provided where the top of walls, etc. would otherwise be unprotected (see Diagram 10). Unless the protection and joints will be a complete barrier to moisture, a damp-proof course should also be provided;
d. damp-proof courses, cavity trays and closers should be provided and designed to ensure that water drains outwards:
i. where the downward flow will be interrupted by an obstruction, such as some types of lintel; and
ii. under openings, unless there is a sill and the sill and its joints will form a complete barrier; and
iii. at abutments between walls and roofs.

Diagram 10 Protection of wall head from precipitation (see paragraph 5.9(c))

Diagram 10 Protection of wall head from precipitation (see paragraph 5.9(c)).
Diagram 10 Protection of wall head from precipitation (see paragraph 5.9(c))

5.10

Insulation. A solid external wall may be insulated on the inside or on the outside. Where it is on the inside a cavity should be provided to give a break in the path for moisture and where it is on the outside it should provide some resistance to the ingress of moisture to ensure the wall remains relatively dry (see Diagram 11).

103 BS 8104:1992 Code of practice for assessing exposure of walls to wind-driven rain.

104 BS 5628-3:2001 Code of practice for use of masonry. Materials and components, design and workmanship.

105 BS EN 998-2:2003 Specification for mortar for masonry. Masontry mortar.

106 BS 5262:1991 Code of practice for external renderings.

Alternative approach

5.11

The requirement can also be met by following the relevant recommendations of BS 5628-3:2001107. The code describes alternative constructions to suit the severity of the exposure and the type of brick or block.