Section 6: Roofs Roofs (resistance to moisture from the outside)

Roofs (resistance to moisture from the outside)

6.3

Roofing can be designed to protect a building from precipitation either by holding the precipitation at the face of the roof or by stopping it from penetrating beyond the back of the roofing system.

6.4

Any roof will meet the requirement if:

a. it is jointless or has sealed joints, and is impervious to moisture (so that moisture will not enter the roofing system); or
b. it has overlapping dry joints, is impervious or weather resisting, and is backed by a material which will direct precipitation which enters the roof towards the outer face (as with roofing felt).

6.5

Some materials can deteriorate rapidly without special care and they should only be used as the weather-resisting part of a roof if certain conditions are met (see Approved Document 7, Materials and workmanship133). The weather-resisting part of a roofing system does not include paint nor does it include any coating, surfacing or rendering which will not itself provide all the weather resistance.

Technical solution

6.6

Roofing systems may be:

a. impervious including metal, plastic and bituminous products; or
b. weather resisting including natural stone or slate, cement based products, fired clay and wood; or
c. moisture resisting including bituminous and plastic products lapped at the joints, if used as a sheet material, and permeable to water vapour unless there is a ventilated space directly behind the material; or
d. jointless materials and sealed joints, which would allow for structural and thermal movement.

6.7

Dry joints between roofing sheets should be designed so that precipitation will not pass through them, or the system should be designed so that precipitation which enters the joints will be drained away without penetrating beyond the back of the roofing system. Note: Whether dry joints are suitable will depend on the design of the joint or the design of the roofing system and the severity of the exposure to wind and rain.

6.8

Each sheet, tile and section of roof should be fixed in an appropriate manner. Guidance as to appropriate fixing methods is given in BS 8000-6:1990134.

Alternative approach

6.9

The requirement can also be met by following the relevant recommendations of:

a. BS CP 143135 for sheet roof and wall coverings made from the following materials:
Part 1:1958 Corrugated and troughed aluminium
Part 5:1964 Zinc
Part 10:1973 Galvanized corrugated steel
Part 12:1970 (1988) Copper
Part 15:1973 (1986) Aluminium
Part 16:1974 Semi-rigid asbestos bitumen sheets.

Recommendations for lead are included in BS 6915:2001136;

b. BS 8219:2001137;
c. BS 8200:1985138;

133 Approved Document 7: Materials and workmanship, DCLG, 2013 edition.

134 BS 8000-6:1990 Workmanship on building sites. Code of practice for slating and tiling of roofs and claddings.

135 BS CP 143 Code of practice for sheet roof and wall coverings.

136 BS 6915:2001 Design and construction of fully supported lead sheet roof and wall coverings. Code of practice.

137 BS 8219:2001 Installation of sheet roof and wall coverings. Profiled fibre cement. Code of practice.

138 BS 8200:1985 Code of practice for the design of nonloadbearing external vertical enclosures of buildings.

d. MCRMA Technical Paper 6139;
e. MCRMA Technical Paper 9140.

These documents describe the materials and contain design considerations including recommendations for fixing.