Section 4: Floors Suspended concrete ground floors (moisture from the ground)

Suspended concrete ground floors (moisture from the ground)

4.17

Any suspended floor of in situ or precast concrete, including beam and block floors, next to the ground will meet the requirement if it will adequately prevent the passage of moisture to the upper surface and if the reinforcement is protected against moisture.

Technical solution

4.18

One solution for a suspended concrete floor could be:

a. in situ concrete at least 100mm thick (but thicker if the structural design requires) containing at least 300kg of cement for each m3 of concrete; or
b. precast concrete construction with or without infilling slabs; and
c. reinforcing steel protected by concrete cover of at least 40mm if the concrete is in situ and at least the thickness required for a moderate exposure if the concrete is precast.

4.19

A suspended concrete floor will meet the requirements if it incorporates:

a. a damp-proof membrane (if the ground below the floor has been excavated below the lowest level of the surrounding ground and will not be effectively drained); and
b. a ventilated air space. This should measure at least 150mm clear from the ground to the underside of the floor (or insulation if provided). Two opposing external walls should have ventilation openings placed so that the ventilating air will have a free path between opposite sides and to all parts of the floor void. The openings should be not less than either 1500mm2/m run of external wall or 500mm2/m2 of floor area, whichever gives the greater opening area. Any pipes needed to carry ventilating air should have a diameter of at least 100mm. Ventilation openings should incorporate suitable grilles which prevent the entry of vermin to the sub-floor but do not resist the air flow unduly.

4.20

In localities where flooding is likely, consideration may be given to including means of inspecting and clearing out the sub-floor voids beneath suspended floors. For guidance, see Improving the flood performance of new buildings – Flood resilient construction8.

8 Improving the flood performance of new buildings – Flood resilient construction, Communities and Local Government, Defra and the Environment Agency, 2007.

90 BS 5628-3:2001 Code of practice for use of masonry. Materials and components, design and workmanship.

91 BS 7331:1990 Specification for direct surfaced wood chipboard based on thermosetting resins.

92 BS EN 312-5:1997 Particleboards. Specifications. Requirements for load-bearing boards for use in humid conditions.

93 BRE Digest 429 Timbers: their natural durability and resistance to preservative treatment, 1998.

94 BS CP 102:1973 Protection of buildings against water from the ground.