Cavity insulation Table 4 Maximum recommended exposure zones for insulated masonry walls

Wall constructionMaximum recommended exposure zone for each construction
Insulation methodMin. width of filled or clear cavity (mm)Impervious claddingRendered finishFacing masonry
Full height of wallAbove facing masonryFull height of wallAbove facing masonryTooled flush jointsRecessed mortar jointsFlush sills and copings
Built-in full fill504333211
754343311
1004443312
1254443312
1504444412
Injected fill not UF foam504232211
754343311
1004343311
1254443312
1504444412
Injected fill
UF foam
504232111
754232211
1004232211
Partial fill
Residual 50mm cavity504444311
Residual 75mm cavity754444411
Residual 100mm cavity1004444421
Internal insulation
Clear cavity 50mm504343311
Clear cavity 100mm1004444422
Fully filled cavity 50mm504333211
Fully filled cavity 100mm1004443312

View this page on RegsUK