Section 5: Walls Cavity insulation

Cavity insulation

5.15

A full or partial fill insulating material may be placed in the cavity between the outer leaf and an inner leaf of masonry subject to the following conditions:

a. The suitability of a wall for installing insulation into the cavity should be determined either by reference to the map in Diagram 12 and the associated Table 4 or following the calculation or assessment procedure in current British or CEN standards. When partial fill materials are to be used, the residual cavity should not be less than 50mm nominal; and
b. A rigid (board or batt) thermal insulating material built into the wall should be the subject of current certification from an appropriate body or a European Technical Approval and the work should be carried out in accordance with the requirements of that document; or
c. Other insulating materials inserted into the cavity after the wall has been constructed should have certification from an appropriate body and be installed in accordance with the appropriate installations code. The suitability of the wall for filling is to be assessed before the work is carried out and the person undertaking the work should operate under an Approved Installer Scheme that includes an assessment of capability. Alternatively the insulating material should be the subject of current certification from an appropriate body or a European Technical Approval and the work should be carried out in accordance with the requirements of that document by operatives either directly employed by the holder of the document or employed by an installer approved to operate under the document; or
d. Urea-formaldehyde foam inserted into the cavity should be in accordance with BS 5617:1985109 and be installed in accordance with BS 5618:1985110. The suitability of the wall for foam filling is to be assessed before the work is carried out and the person undertaking the work should operate under an Approved Installer Scheme that includes an assessment of capability.
e. When the cavity of an existing house is being filled, special attention should be given to the condition of the external leaf of the wall, e.g. its state of repair and type of pointing. Guidance is given in BS 8208-1:1985111. Some materials that are used to fill existing cavity walls may have a low risk of moisture being carried over to the internal leaf of the wall. In cases where a third party assessment of such a cavity fill material contains a method of assessing the construction of the walls and exposure risk, the procedure set out below may be replaced by that method.

107 BS 5628-3:2001 Code of practice for use of masonry. Materials and components, design and workmanship.

108 BS 5628-3:2001 Code of practice for use of masonry. Materials and components, design and workmanship.

109 BS 5617:1985 Specification for urea-formaldehyde (UF) foam systems suitable for thermal insulation of cavity walls with masonry or concrete inner and outer leaves.

110 BS 5618:1985 Code of practice for thermal insulation of cavity walls (with masonry or concrete inner and outer leaves) by filling with urea-formaldehyde (UF) foam systems.

111 BS 8208-1:1985 Guide to assessment of suitability of external cavity walls for filling with thermal insulation.

Diagram 11 Insulated external walls: examples (see paragraphs 5.10, 5.13 and 5.17)

Diagram 11 Insulated external walls: examples (see paragraphs 5.10, 5.13 and 5.17).
Diagram 11 Insulated external walls: examples (see paragraphs 5.10, 5.13 and 5.17)

Diagram 12 UK zones for exposure to driving rain

Diagram 12 UK zones for exposure to driving rain.
Diagram 12 UK zones for exposure to driving rain
Wall constructionMaximum recommended exposure zone for each construction
Insulation methodMin. width of filled or clear cavity (mm)Impervious claddingRendered finishFacing masonry
Full height of wallAbove facing masonryFull height of wallAbove facing masonryTooled flush jointsRecessed mortar jointsFlush sills and copings
Built-in full fill504333211
754343311
1004443312
1254443312
1504444412
Injected fill not UF foam504232211
754343311
1004343311
1254443312
1504444412
Injected fill
UF foam
504232111
754232211
1004232211
Partial fill
Residual 50mm cavity504444311
Residual 75mm cavity754444411
Residual 100mm cavity1004444421
Internal insulation
Clear cavity 50mm504343311
Clear cavity 100mm1004444422
Fully filled cavity 50mm504333211
Fully filled cavity 100mm1004443312

5.16

If the map given in Diagram 12 is used, determine the national exposure and, where appropriate, apply the following modifiers:

i. where local conditions accentuate wind effects, such as open hillsides or valleys where the wind is funnelled onto the wall, add one to this exposure zone value;
ii. where walls do not face into the prevailing wind, subtract one from this exposure zone value.

(The national exposure zone value can be more accurately calculated from the larger scale maps and correction factors given in BS 8104:1992112.)

112 BS 8104:1992 Code of practice for assessing exposure of walls to wind-driven rain.

Determine the recommended constructions from the modified exposure zone values given in Table 4. Further guidance as to the use of this table is given in BRE Report 262113.