Section 5: Walls Cavity insulation
Cavity insulation
5.15
A full or partial fill insulating material may be placed in the cavity between the outer leaf and an inner leaf of masonry subject to the following conditions:
107 BS 5628-3:2001 Code of practice for use of masonry. Materials and components, design and workmanship.
108 BS 5628-3:2001 Code of practice for use of masonry. Materials and components, design and workmanship.
109 BS 5617:1985 Specification for urea-formaldehyde (UF) foam systems suitable for thermal insulation of cavity walls with masonry or concrete inner and outer leaves.
110 BS 5618:1985 Code of practice for thermal insulation of cavity walls (with masonry or concrete inner and outer leaves) by filling with urea-formaldehyde (UF) foam systems.
111 BS 8208-1:1985 Guide to assessment of suitability of external cavity walls for filling with thermal insulation.
Diagram 11 Insulated external walls: examples (see paragraphs 5.10, 5.13 and 5.17)

Diagram 12 UK zones for exposure to driving rain

Table 4 Maximum recommended exposure zones for insulated masonry walls
| Wall construction | Maximum recommended exposure zone for each construction | |||||||
|---|---|---|---|---|---|---|---|---|
| Insulation method | Min. width of filled or clear cavity (mm) | Impervious cladding | Rendered finish | Facing masonry | ||||
| Full height of wall | Above facing masonry | Full height of wall | Above facing masonry | Tooled flush joints | Recessed mortar joints | Flush sills and copings | ||
| Built-in full fill | 50 | 4 | 3 | 3 | 3 | 2 | 1 | 1 |
| 75 | 4 | 3 | 4 | 3 | 3 | 1 | 1 | |
| 100 | 4 | 4 | 4 | 3 | 3 | 1 | 2 | |
| 125 | 4 | 4 | 4 | 3 | 3 | 1 | 2 | |
| 150 | 4 | 4 | 4 | 4 | 4 | 1 | 2 | |
| Injected fill not UF foam | 50 | 4 | 2 | 3 | 2 | 2 | 1 | 1 |
| 75 | 4 | 3 | 4 | 3 | 3 | 1 | 1 | |
| 100 | 4 | 3 | 4 | 3 | 3 | 1 | 1 | |
| 125 | 4 | 4 | 4 | 3 | 3 | 1 | 2 | |
| 150 | 4 | 4 | 4 | 4 | 4 | 1 | 2 | |
| Injected fill UF foam | 50 | 4 | 2 | 3 | 2 | 1 | 1 | 1 |
| 75 | 4 | 2 | 3 | 2 | 2 | 1 | 1 | |
| 100 | 4 | 2 | 3 | 2 | 2 | 1 | 1 | |
| Partial fill | ||||||||
| Residual 50mm cavity | 50 | 4 | 4 | 4 | 4 | 3 | 1 | 1 |
| Residual 75mm cavity | 75 | 4 | 4 | 4 | 4 | 4 | 1 | 1 |
| Residual 100mm cavity | 100 | 4 | 4 | 4 | 4 | 4 | 2 | 1 |
| Internal insulation | ||||||||
| Clear cavity 50mm | 50 | 4 | 3 | 4 | 3 | 3 | 1 | 1 |
| Clear cavity 100mm | 100 | 4 | 4 | 4 | 4 | 4 | 2 | 2 |
| Fully filled cavity 50mm | 50 | 4 | 3 | 3 | 3 | 2 | 1 | 1 |
| Fully filled cavity 100mm | 100 | 4 | 4 | 4 | 3 | 3 | 1 | 2 |
5.16
If the map given in Diagram 12 is used, determine the national exposure and, where appropriate, apply the following modifiers:
(The national exposure zone value can be more accurately calculated from the larger scale maps and correction factors given in BS 8104:1992112.)
112 BS 8104:1992 Code of practice for assessing exposure of walls to wind-driven rain.
Determine the recommended constructions from the modified exposure zone values given in Table 4. Further guidance as to the use of this table is given in BRE Report 262113.