Section 1: Simplified method Removing excess heat

Removing excess heat

1.10

Buildings or parts of buildings with cross-ventilation should equal or exceed the minimum free areas in Table 1.3.

Table 1.3 Minimum free areas for buildings or parts of buildings with cross-ventilation

High risk locationModerate risk location
Total minimum free area(1)The greater of the following: a. 6% of the floor area(2) b. 70% of the glazing area(3)The greater of the following: a. 9% of the floor area(2) b. 55% of the glazing area(3)
Bedroom minimum free area13% of the floor area of the room(4)4% of the floor area of the room(4)

NOTES:

1. The total minimum free area is the free area for the whole dwellinghouse, residential unit, shared communal room or common space, including any bedrooms.
2. ‘Floor area’ is a key term. See Appendix A.
3. ‘Glazing area’ is a key term. See Appendix A.
4. ‘Floor area of the room’ is a key term. See Appendix A.

1.11

Buildings or parts of buildings with no cross-ventilation should equal or exceed the minimum free areas in Table 1.4.

Table 1.4 Minimum free areas for buildings or parts of buildings without cross-ventilation

High risk locationModerate risk location
Total minimum free area(1)The greater of the following: a. 10% of the floor area(2) b. 95% of the glazing area(3)The greater of the following: a. 12% of the floor area(2) b. 80% of the glazing area(3)
Bedroom minimum free area13% of the floor area of the room(4)4% of the floor area of the room(4)

NOTES:

1. The total minimum free area is the free area for the whole dwellinghouse, residential unit, shared communal room or common space, including any bedrooms.
2. ‘Floor area’ is a key term. See Appendix A.
3. ‘Glazing area’ is a key term. See Appendix A.
4. ‘Floor area of the room’ is a key term. See Appendix A.

1.12

Openings should be designed to achieve the free areas in paragraphs 1.10 and 1.11. The equivalent area of the opening should meet or exceed the free area of the opening. The equivalent area of the opening should be assessed by either of the following means.

a. Measurement of the product to BS EN 13141-1.
b. Calculation using Appendix D.

NOTE: A system for purge ventilation should be provided in each habitable room to demonstrate compliance with Part F of the Building Regulations. The guidance in Section 1 of Approved Document F, Volume 1: Dwellings gives minimum standards for purge ventilation. When following this simplified method, applying the guidance in paragraphs 1.10 to 1.12 will usually result in free areas that exceed the free areas in Approved Document F, Volume 1: Dwellings.

1.13

The simplified method is not suitable for buildings with more than one residential unit which use a communal heating or hot water system with significant amounts of horizontal heating or hot water distribution pipework. Main distribution routes should be through vertical risers to minimise heat gains into common spaces.