Section 2: Dynamic thermal modelling
Section 2: Dynamic thermal modelling
2.1
This section details a dynamic thermal modelling method for demonstrating compliance with requirement O1. It provides a standardised approach to predicting overheating risk for residential buildings using dynamic thermal modelling as an alternative to the simplified method in Section 1.
2.2
The methodology is suitable for all residential buildings. It may offer the designer additional design flexibility over the solutions in Section 1 in the following situations.
NOTE: Local microclimates may not be well reflected by the geographically closest weather file.
Dynamic thermal modelling method
2.3
To demonstrate compliance using the dynamic thermal modelling method, all of the following guidance should be followed.
2.4
The building control body should be provided with a report that demonstrates that the residential building passes CIBSE’s TM59 assessment of overheating. This report should contain the details in CIBSE’s TM59, section 2.3.
NOTE: Appendix B of this approved document includes a compliance checklist. The designer may use this checklist to demonstrate compliance to the building control body.
Limits on CIBSE’s TM59 modelling
2.5
CIBSE’s TM59 method requires the modeller to make choices. The dynamic thermal modelling method in this section applies limits to these choices, which are detailed in paragraph 2.6. These limits should be applied when following the guidance in CIBSE’s TM59.
2.6
All of the following limits on CIBSE’s TM59, section 3.3, apply.
Acceptable strategies for reducing overheating risk
Limiting solar gains
2.7
Solar gains in summer should be limited by any of the following means.
2.8
Although internal blinds and curtains provide some reduction in solar gains, they should not be taken into account when considering whether requirement O1 has been met.
2.9
Foliage, such as tree cover, can provide some reduction in solar gains. However, it should not be taken into account when considering whether requirement O1 has been met.
NOTE: Examples of solar shading and their effectiveness are provided in the Building Research Establishment’s BR 364 Solar Shading of Buildings.
Removing excess heat
2.10
Excess heat should be removed from the residential building by any of the following means.
2.11
The building should be constructed to meet requirement O1 using passive means as far as reasonably practicable. It should be demonstrated to the building control body that all practicable passive means of limiting unwanted solar gains and removing excess heat have been used first before adopting mechanical cooling. Any mechanical cooling (air-conditioning) is expected to be used only where requirement O1 cannot be met using openings.
NOTE: Any method to reduce overheating risk in residential buildings must comply with all other parts of the Building Regulations. Particular attention should be paid to the requirements of Part F and the guidance in Approved Document F, Volume 1: Dwellings on noise and maintenance.
NOTE: A system for purge ventilation should be provided in each habitable room to demonstrate compliance with Part F of the Building Regulations. The guidance in Section 1 of Approved Document F, Volume 1: Dwellings should be followed for the minimum standards for purge ventilation. A larger amount of purge ventilation may be required than that in Approved Document F, Volume 1: Dwellings in order to satisfy requirement O1 on providing an adequate means to remove excess heat from the indoor environment.