Limiting solar gains Table 1.1 Limiting solar gains for buildings or parts of buildings with cross-ventilation(1)
Table 1.1 Limiting solar gains for buildings or parts of buildings with cross-ventilation(1)
| High risk location | Moderate risk location | |||
|---|---|---|---|---|
| Largest glazed façade orientation | Maximum area of glazing (% floor area) | Maximum area of glazing in the most glazed room (% floor area of room) | Maximum area of glazing (% floor area) | Maximum area of glazing in the most glazed room (% floor area of room) |
| North | 15 | 37 | 18 | 37 |
| East | 18 | 37 | 18 | 37 |
| South | 15 | 22 | 15 | 30 |
| West | 18 | 37 | 11 | 22 |
NOTE:
1. Floor area and floor area of room are as defined in Appendix A.