Section 1: Simplified method Limiting solar gains
Limiting solar gains
1.6
To limit solar gains, all of the following standards should be followed.
a. The maximum glazing area of the building or part of the building given in Table 1.1 or Table 1.2. This should be determined using the orientation of the façade that has the largest area of glazing.
b. The maximum glazing area of the most glazed room given in Table 1.1 or Table 1.2. This should be determined using the orientation of the façade that has the largest area of glazing.
c. Shading for buildings in the high risk location, following paragraph 1.9.
1.7
Buildings or parts of buildings with cross-ventilation should not exceed the maximum glazing areas in Table 1.1.
Table 1.1 Limiting solar gains for buildings or parts of buildings with cross-ventilation(1)
| High risk location | Moderate risk location | |||
|---|---|---|---|---|
| Largest glazed façade orientation | Maximum area of glazing (% floor area) | Maximum area of glazing in the most glazed room (% floor area of room) | Maximum area of glazing (% floor area) | Maximum area of glazing in the most glazed room (% floor area of room) |
| North | 15 | 37 | 18 | 37 |
| East | 18 | 37 | 18 | 37 |
| South | 15 | 22 | 15 | 30 |
| West | 18 | 37 | 11 | 22 |
NOTE:
1. Floor area and floor area of room are as defined in Appendix A.
1.8
Buildings or parts of buildings with no cross-ventilation should not exceed the maximum glazing areas in Table 1.2.
Table 1.2 Limiting solar gains for buildings or parts of buildings without cross-ventilation(1)
| High risk location | Moderate risk location | |||
|---|---|---|---|---|
| Largest glazed façade orientation | Maximum area of glazing (% floor area) | Maximum area of glazing in the most glazed room (% floor area of room) | Maximum area of glazing (% floor area) | Maximum area of glazing in the most glazed room (% floor area of room) |
| North | 15 | 26 | 18 | 26 |
| East | 11 | 18 | 18 | 26 |
| South | 11 | 11 | 15 | 15 |
| West | 11 | 18 | 11 | 11 |
NOTE:
1. Floor area and floor area of room are as defined in Appendix A.
1.9
Residential buildings in the high risk location should, in addition to following the maximum glazing areas in Table 1.1 and Table 1.2, provide shading for glazed areas between compass points north-east and north-west via the south. Shading should be provided by one of the following means.
a. External shutters with means of ventilation.
b. Glazing with a maximum g-value of 0.4 and a minimum light transmittance of 0.7.
c. Overhangs with 50 degrees altitude cut-off on due south-facing façades only.