Limiting solar gains Table 1.2 Limiting solar gains for buildings or parts of buildings without cross-ventilation(1)

Table 1.2 Limiting solar gains for buildings or parts of buildings without cross-ventilation(1)

High risk locationModerate risk location
Largest glazed façade orientationMaximum area of glazing (% floor area)Maximum area of glazing in the most glazed room (% floor area of room)Maximum area of glazing (% floor area)Maximum area of glazing in the most glazed room (% floor area of room)
North15261826
East11181826
South11111515
West11181111

NOTE:

1. Floor area and floor area of room are as defined in Appendix A.