Limiting solar gains Table 1.2 Limiting solar gains for buildings or parts of buildings without cross-ventilation(1)
Table 1.2 Limiting solar gains for buildings or parts of buildings without cross-ventilation(1)
| High risk location | Moderate risk location | |||
|---|---|---|---|---|
| Largest glazed façade orientation | Maximum area of glazing (% floor area) | Maximum area of glazing in the most glazed room (% floor area of room) | Maximum area of glazing (% floor area) | Maximum area of glazing in the most glazed room (% floor area of room) |
| North | 15 | 26 | 18 | 26 |
| East | 11 | 18 | 18 | 26 |
| South | 11 | 11 | 15 | 15 |
| West | 11 | 18 | 11 | 11 |
NOTE:
1. Floor area and floor area of room are as defined in Appendix A.