Installation and specification of fire dampers 10.19
10.19
Fire dampers should meet both of the following conditions.
a. Conform to BS EN 15650.
b. Have a minimum E classification of 60 minutes or to match the integrity rating of the fire resisting elements, whichever is higher.
10.20Fire and smoke dampers should meet both of the following conditions.
a. Conform to BS EN 15650.