Section 10: Protection of openings and fire-stopping Mechanical ventilation and air-conditioning systems

Mechanical ventilation and air-conditioning systems

General provisions

10.6

Ductwork should not help to transfer fire and smoke through the building. Terminals of exhaust points should be sited away from final exits, cladding or roofing materials achieving class B-s3, d2 or worse and openings into the building.

10.7

Ventilation ducts supplying or extracting air directly to or from a protected stairway should not also serve other areas. A separate ventilation system should be provided for each protected stairway.

10.8

A fire and smoke damper should be provided where ductwork enters or leaves each section of the protected escape route it serves. It should be operated by a smoke detector or suitable fire detection system. Fire and smoke dampers should close when smoke is detected. Alternatively, the methods set out in paragraphs 10.15 and 10.16 and Diagrams 10.2 and 10.3 may be followed.

10.9

In a system that recirculates air, smoke detectors should be fitted in the extract ductwork before both of the following.

a. The point where recirculated air is separated from air to be discharged to the outside.
b. Any filters or other air cleaning equipment.

When smoke is detected, detectors should do one of the following.

a. Cause the system to immediately shut down.
b. Switch the ventilation system from recirculating mode to extraction to divert smoke outside the building.

10.10

Non-domestic kitchens, car parks and plant rooms should have separate and independent extraction systems. Extracted air should not be recirculated.

10.11

Under fire conditions, ventilation and air-conditioning systems should be compatible with smoke control systems and need to be considered in their respective design.

Ventilation ducts and flues passing through fire-separating elements

General provisions

10.12

If air handling ducts pass through fire-separating elements, the fire performance of the elements should be maintained using one or more of the following four methods. In most ductwork systems, a combination of the four methods is best.

a. Method 1 – thermally activated fire dampers.
b. Method 2 – fire resisting enclosures.
c. Method 3 – protection using fire resisting ductwork.
d. Method 4 – automatically activated fire and smoke dampers triggered by smoke detectors.

10.13

Further information on fire resisting ductwork is given in the ASFP Blue Book.

Kitchen extract

10.14

Methods 1 and 4 should not be used for extract ductwork serving kitchens. The likely build-up of grease within the duct can adversely affect dampers.

Ducts passing through protected escape routes

10.15

Method 1 should not be used for extract ductwork passing through the enclosures of protected escape routes (Diagrams 10.2 and 10.3), as large volumes of smoke can pass thermal devices without triggering them.

10.16

An ES classified fire and smoke damper which is activated by a suitable fire detection system (method 4) may also be used for protected escape routes.

Diagram 10.2 Ductwork passing through protected escape routes – method 2 or method 3

Diagram 10.2 Ductwork passing through protected escape routes – method 2 or method 3. Wording on the drawing: See para 10.15; Ductwork enclosed in fire resisting construction classified EI X in accordance with BS EN 13501-2 (fire exposure from the duct side), or fire resisting ductwork classified EIS X in accordance with BS EN 13501-3, where X is the fire resistance rating (in minutes) of the walls of the protected escape route; Ductwork serving area; Fd; Fd; Protected stairway; Protected lobby; Ductwork serving area; Fd; Fire doorset; Ductwork serving area; Fd; NOTE: Ventilation ducts which serve other parts of the building should not supply or extract air directly to or from a protected escape route.
Diagram 10.2 Ductwork passing through protected escape routes – method 2 or method 3

Diagram 10.3 Ductwork passing through protected escape routes – method 4

Diagram 10.3 Ductwork passing through protected escape routes – method 4. Wording on the drawing: See para 10.15; ES leakage rated fire and smoke damper conforming to BS EN 13501-3/BS EN 1366-2; Protected stairway; Fd; Protected lobby; Fd; SD SD; Smoke detection system in accordance with BS 5839-1 to activate ES damper; SD; Fd Fire doorset Ductwork serving area; Ductwork serving area; NOTE: Ventilation ducts which serve other parts of the building should not supply or extract air directly to or from a protected escape route.; Fd
Diagram 10.3 Ductwork passing through protected escape routes – method 4

Installation and specification of fire dampers

10.17

Both fire dampers and fire and smoke dampers should be all of the following.

a. Sited within the thickness of the fire-separating elements.
b. Securely fixed.
c. Sited such that, in a fire, expansion of the ductwork would not push the fire damper through the structure.

10.18

Access to the fire damper and its actuating mechanism should be provided for inspection, testing and maintenance.

10.19

Fire dampers should meet both of the following conditions.

a. Conform to BS EN 15650.
b. Have a minimum E classification of 60 minutes or to match the integrity rating of the fire resisting elements, whichever is higher.

10.20Fire and smoke dampers should meet both of the following conditions.

a. Conform to BS EN 15650.
b. Have a minimum ES classification of 60 minutes or to match the integrity rating of the fire resisting elements, whichever is higher.

10.21

Smoke detectors should be sited so as to prevent the spread of smoke as early as practicable by activating the fire and smoke dampers. Smoke detectors and automatic release mechanisms used to activate fire dampers and/or fire and smoke dampers should conform to BS EN 54-7 and BS 5839-3 respectively.

Further information on fire dampers and/or fire and smoke dampers is given in the ASFP Grey Book.

Sleeping risks

10.22

Where the use of the building involves a sleeping risk, fire dampers or fire and smoke dampers should be actuated by both of the following.

a. Smoke detector-controlled automatic release mechanisms.
b. Thermally actuated devices.

However, in a situation where both of the following are true:

a. all occupants of the building can be expected to make an unaided escape
b. an L1 fire detection and alarm system is installed in accordance with BS 5839-1

then both of the following exceptions may be made.

i. If, on the detection of smoke, the fire alarm system signals the immediate evacuation of all the occupants of the building, then fire dampers and/or fire and smoke dampers do not need to be actuated by smoke detectors.
ii. If the building is divided into fire compartments and the alarm system is arranged to signal the immediate evacuation of the occupants of the fire compartment in which the fire has been detected, then smoke detector-operated fire dampers or fire and smoke dampers need only be provided where ductwork enters or leaves the fire compartment.