Section 10: Protection of openings and fire-stopping Mechanical ventilation and air-conditioning systems
Mechanical ventilation and air-conditioning systems
General provisions
10.6
Ductwork should not help to transfer fire and smoke through the building. Terminals of exhaust points should be sited away from final exits, cladding or roofing materials achieving class B-s3, d2 or worse and openings into the building.
10.7
Ventilation ducts supplying or extracting air directly to or from a protected stairway should not also serve other areas. A separate ventilation system should be provided for each protected stairway.
10.8
A fire and smoke damper should be provided where ductwork enters or leaves each section of the protected escape route it serves. It should be operated by a smoke detector or suitable fire detection system. Fire and smoke dampers should close when smoke is detected. Alternatively, the methods set out in paragraphs 10.15 and 10.16 and Diagrams 10.2 and 10.3 may be followed.
10.9
In a system that recirculates air, smoke detectors should be fitted in the extract ductwork before both of the following.
When smoke is detected, detectors should do one of the following.
10.10
Non-domestic kitchens, car parks and plant rooms should have separate and independent extraction systems. Extracted air should not be recirculated.
10.11
Under fire conditions, ventilation and air-conditioning systems should be compatible with smoke control systems and need to be considered in their respective design.
Ventilation ducts and flues passing through fire-separating elements
General provisions
10.12
If air handling ducts pass through fire-separating elements, the fire performance of the elements should be maintained using one or more of the following four methods. In most ductwork systems, a combination of the four methods is best.
10.13
Further information on fire resisting ductwork is given in the ASFP Blue Book.
Kitchen extract
10.14
Methods 1 and 4 should not be used for extract ductwork serving kitchens. The likely build-up of grease within the duct can adversely affect dampers.
Ducts passing through protected escape routes
10.15
Method 1 should not be used for extract ductwork passing through the enclosures of protected escape routes (Diagrams 10.2 and 10.3), as large volumes of smoke can pass thermal devices without triggering them.
10.16
An ES classified fire and smoke damper which is activated by a suitable fire detection system (method 4) may also be used for protected escape routes.
Diagram 10.2 Ductwork passing through protected escape routes – method 2 or method 3

Diagram 10.3 Ductwork passing through protected escape routes – method 4

Installation and specification of fire dampers
10.17
Both fire dampers and fire and smoke dampers should be all of the following.
10.18
Access to the fire damper and its actuating mechanism should be provided for inspection, testing and maintenance.
10.19
Fire dampers should meet both of the following conditions.
10.20Fire and smoke dampers should meet both of the following conditions.
10.21
Smoke detectors should be sited so as to prevent the spread of smoke as early as practicable by activating the fire and smoke dampers. Smoke detectors and automatic release mechanisms used to activate fire dampers and/or fire and smoke dampers should conform to BS EN 54-7 and BS 5839-3 respectively.
Further information on fire dampers and/or fire and smoke dampers is given in the ASFP Grey Book.
Sleeping risks
10.22
Where the use of the building involves a sleeping risk, fire dampers or fire and smoke dampers should be actuated by both of the following.
However, in a situation where both of the following are true:
then both of the following exceptions may be made.