Installation and specification of fire dampers 10.22
10.22
Where the use of the building involves a sleeping risk, fire dampers or fire and smoke dampers should be actuated by both of the following.
a. Smoke detector-controlled automatic release mechanisms.
b. Thermally actuated devices.
However, in a situation where both of the following are true:
a. all occupants of the building can be expected to make an unaided escape
b. an L1 fire detection and alarm system is installed in accordance with BS 5839-1
then both of the following exceptions may be made.
i. If, on the detection of smoke, the fire alarm system signals the immediate evacuation of all the occupants of the building, then fire dampers and/or fire and smoke dampers do not need to be actuated by smoke detectors.
ii. If the building is divided into fire compartments and the alarm system is arranged to signal the immediate evacuation of the occupants of the fire compartment in which the fire has been detected, then smoke detector-operated fire dampers or fire and smoke dampers need only be provided where ductwork enters or leaves the fire compartment.