General provisions 10.9

10.9

In a system that recirculates air, smoke detectors should be fitted in the extract ductwork before both of the following.

a. The point where recirculated air is separated from air to be discharged to the outside.
b. Any filters or other air cleaning equipment.

When smoke is detected, detectors should do one of the following.

a. Cause the system to immediately shut down.
b. Switch the ventilation system from recirculating mode to extraction to divert smoke outside the building.