Buildings fitted with fire mains 15.4
15.4
For buildings fitted with dry fire mains, both of the following apply.
a. Access should be provided for a pumping appliance to within 18m of each fire main inlet connection point. Inlets should be on the face of the building.
b. The fire main inlet connection point should be visible from the parking position of the appliance, and satisfy paragraph 16.10.