Section 15: Vehicle access Buildings fitted with fire mains

Buildings fitted with fire mains

15.4

For buildings fitted with dry fire mains, both of the following apply.

a. Access should be provided for a pumping appliance to within 18m of each fire main inlet connection point. Inlets should be on the face of the building.
b. The fire main inlet connection point should be visible from the parking position of the appliance, and satisfy paragraph 16.10.

15.5

For buildings fitted with wet fire mains, access for a pumping appliance should comply with both of the following.

a. Within 18m, and within sight of, an entrance giving access to the fire main.
b. Within sight of the inlet to replenish the suction tank for the fire main in an emergency.

15.6

Where fire mains are provided in buildings for which Sections 16 and 17 make no provision, vehicle access may be as described in paragraphs 15.4 and 15.5, rather than Table 15.1.