Section 15: Vehicle access
Section 15: Vehicle access
Buildings not fitted with fire mains
15.1
For small buildings (up to 2000m2, with a top storey that is a maximum of 11m above ground level), vehicle access for a pump appliance should be provided to whichever is the less onerous of the following.
15.2
For all other buildings, provide vehicle access in accordance with Table 15.1.
15.3
Every elevation to which vehicle access is provided should have a door, a minimum of 750mm wide, to give access into the building. The maximum distance between doors, or between a door and the end of the elevation, is 60m (e.g. a 150m elevation would need a minimum of two doors).
Table 15.1 Fire and rescue service vehicle access to buildings not fitted with fire mains
| Total floor area(1) of building (m²) | Height of floor of top storey above ground (m)(2) | Provide vehicle access to: | Type of appliance |
|---|---|---|---|
| Up to 2000 | Up to 11 | See paragraph 15.1 | Pump |
| Over 11 | 15% of perimeter | High reach | |
| 2000–8000 | Up to 11 | 15% of perimeter | Pump |
| Over 11 | 50% of perimeter | High reach | |
| 8000–16,000 | Up to 11 | 50% of perimeter | Pump |
| Over 11 | 50% of perimeter | High reach | |
| 16,000–24,000 | Up to 11 | 75% of perimeter | Pump |
| Over 11 | 75% of perimeter | High reach | |
| Over 24,000 | Up to 11 | 100% of perimeter | Pump |
| Over 11 | 100% of perimeter | High reach |
NOTES:
Diagram 15.1 Example of building footprint and perimeter

Buildings fitted with fire mains
15.4
For buildings fitted with dry fire mains, both of the following apply.
15.5
For buildings fitted with wet fire mains, access for a pumping appliance should comply with both of the following.
15.6
Where fire mains are provided in buildings for which Sections 16 and 17 make no provision, vehicle access may be as described in paragraphs 15.4 and 15.5, rather than Table 15.1.
Design of access routes and hardstandings
15.7
Access routes and hardstandings should comply with the guidance in Table 15.2. Requirements can only apply to the site of the works.
It may not be reasonable to upgrade the route across a site to a small building. The building control body, in consultation with the fire and rescue service, should consider options from doing no work to upgrading certain features, such as sharp bends.
15.8
Where access to an elevation is provided in accordance with Table 15.1, the following requirements should be met, depending on the building height.
15.9
Where access is provided for high reach appliances in accordance with Table 15.1, overhead obstructions (such as cables and branches) should be avoided in the zone shown in Diagram 15.2.
15.10
Dead-end access routes longer than 20m require turning facilities, as in Diagram 15.3. Turning facilities should comply with the guidance in Table 15.2.
Table 15.2 Typical fire and rescue service vehicle access route specification
| Appliance type | Minimum width of road between kerbs (m) | Minimum width of gateways (m) | Minimum turning circle between kerbs (m) | Minimum turning circle between walls (m) | Minimum clearance height (m) | Minimum carrying capacity (tonnes) |
|---|---|---|---|---|---|---|
| Pump | 3.7 | 3.1 | 16.8 | 19.2 | 3.7 | 12.5 |
| High reach | 3.7 | 3.1 | 26.0 | 29.0 | 4.0 | 17.0 |
NOTES:
Diagram 15.2 Relationship between building and hardstanding/access roads for high reach fire appliances

Diagram 15.3 Turning facilities