Section 15: Vehicle access

Section 15: Vehicle access

Buildings not fitted with fire mains

15.1

For small buildings (up to 2000m2, with a top storey that is a maximum of 11m above ground level), vehicle access for a pump appliance should be provided to whichever is the less onerous of the following.

a. 15% of the perimeter.
b. Within 45m of every point of the footprint of the building (see Diagram 15.1).

15.2

For all other buildings, provide vehicle access in accordance with Table 15.1.

15.3

Every elevation to which vehicle access is provided should have a door, a minimum of 750mm wide, to give access into the building. The maximum distance between doors, or between a door and the end of the elevation, is 60m (e.g. a 150m elevation would need a minimum of two doors).

Table 15.1 Fire and rescue service vehicle access to buildings not fitted with fire mains

Total floor area(1) of building (m²)Height of floor of top storey above ground (m)(2) Provide vehicle access to:Type of appliance
Up to 2000Up to 11See paragraph 15.1Pump
Over 1115% of perimeterHigh reach
2000–8000Up to 1115% of perimeterPump
Over 1150% of perimeterHigh reach
8000–16,000Up to 1150% of perimeterPump
Over 1150% of perimeterHigh reach
16,000–24,000Up to 1175% of perimeterPump
Over 1175% of perimeterHigh reach
Over 24,000Up to 11100% of perimeterPump
Over 11100% of perimeterHigh reach

NOTES:

1. The sum of the area of all storeys in the building (excluding basements).
2. For storage buildings (purpose group 7(a)), measure height to mean roof level (see Appendix D).

Diagram 15.1 Example of building footprint and perimeter

Diagram 15.1 Example of building footprint and perimeter. Wording on the drawing: See para 15.1; C D; A B; E F; J I L K H G; N M; Plan of building AFGL where AL and FG are walls in common with other buildings.; If the dimensions of the building are such that Table 15.1 requires vehicle access, the green shaded area illustrates one possible example of 15% of the perimeter. Note: There should be a door into the building in this length (see paragraph 15.3).; The footprint of the building is the maximum aggregate plan perimeter found by the vertical projection of any overhanging storey onto a ground storey (i.e. ABCDEFGHMNKL).; If the building does not have walls in common with other buildings, the lengths AL and FG would be included in the perimeter.; The perimeter of the building for the purposes of Table 15.1 is the sum of the lengths of the two external walls, taking account of the footprint, i.e. (A to B to C to D to E to F) + (G to H to M to N to K to L).
Diagram 15.1 Example of building footprint and perimeter

Buildings fitted with fire mains

15.4

For buildings fitted with dry fire mains, both of the following apply.

a. Access should be provided for a pumping appliance to within 18m of each fire main inlet connection point. Inlets should be on the face of the building.
b. The fire main inlet connection point should be visible from the parking position of the appliance, and satisfy paragraph 16.10.

15.5

For buildings fitted with wet fire mains, access for a pumping appliance should comply with both of the following.

a. Within 18m, and within sight of, an entrance giving access to the fire main.
b. Within sight of the inlet to replenish the suction tank for the fire main in an emergency.

15.6

Where fire mains are provided in buildings for which Sections 16 and 17 make no provision, vehicle access may be as described in paragraphs 15.4 and 15.5, rather than Table 15.1.

Design of access routes and hardstandings

15.7

Access routes and hardstandings should comply with the guidance in Table 15.2. Requirements can only apply to the site of the works.

It may not be reasonable to upgrade the route across a site to a small building. The building control body, in consultation with the fire and rescue service, should consider options from doing no work to upgrading certain features, such as sharp bends.

15.8

Where access to an elevation is provided in accordance with Table 15.1, the following requirements should be met, depending on the building height.

a. Buildings up to 11m, excluding small buildings (paragraph 15.1): pump appliance access should be provided adjacent to the building for the specified percentage of the total perimeter.
b. Buildings over 11m: access routes should comply with the guidance in Diagram 15.2.

15.9

Where access is provided for high reach appliances in accordance with Table 15.1, overhead obstructions (such as cables and branches) should be avoided in the zone shown in Diagram 15.2.

15.10

Dead-end access routes longer than 20m require turning facilities, as in Diagram 15.3. Turning facilities should comply with the guidance in Table 15.2.

Table 15.2 Typical fire and rescue service vehicle access route specification

Appliance typeMinimum width of road between kerbs (m)Minimum width of gateways (m)Minimum turning circle between kerbs (m)Minimum turning circle between walls (m)Minimum clearance height (m)Minimum carrying capacity (tonnes)
Pump3.73.116.819.23.712.5
High reach3.73.126.029.04.017.0

NOTES:

1. Fire appliances are not standardised. The building control body may, in consultation with the local fire and rescue service, use other dimensions.
2. The roadbase can be designed to 12.5 tonne capacity. Structures such as bridges should have the full 17-tonne capacity. The weight of high reach appliances is distributed over a number of axles, so infrequent use of a route designed to accommodate 12.5 tonnes should not cause damage.

Diagram 15.2 Relationship between building and hardstanding/access roads for high reach fire appliances

Diagram 15.2 Relationship between building and hardstanding/access roads for high reach fire appliances. Wording on the drawing: See paras 15.8 and 15.9; Overhead obstructions to be avoided in this zone; Face of building at ground level or vertical plane of projecting upper storey; a; b; c d; Obstruction; Hardstanding or access road; Type of appliance; Turntable Hydraulic ladder platform dimension (m) dimension (m); a. Maximum distance of near edge of hardstanding from building 4.9 2.0 b. Minimum width of hardstanding 5.0 5.5 c. Minimum distance of further edge of hardstanding from building 10.0 7.5 d. Minimum width of unobstructed space (for swing of appliance platform) N/A 2.2; NOTES:; 2. Fire appliances are not standardised. Some fire services have 1. Hardstanding for high reach appliances should be as appliances with a greater weight or di°erent size. level as possible and should have a maximum In consultation with the fire and rescue service, the building gradient of 1 in 12. control body should adopt the relevant dimensions and ground loading capacity.
Diagram 15.2 Relationship between building and hardstanding/access roads for high reach fire appliances

Diagram 15.3 Turning facilities

Diagram 15.3 Turning facilities. Wording on the drawing: See para 15.10; Fire and rescue service vehicles should not have to reverse more than 20m from the end of an access road.; Turning circle, hammerhead or other point at which vehicle can turn; Exit Building; 20m max.
Diagram 15.3 Turning facilities

View this page on RegsUK