Provision of firefighting shafts 17.6

17.6

At least two firefighting shafts, which do not need to include firefighting lifts, should be provided if buildings meet all of the following.

a. They are in the ‘shop and commercial’, ‘assembly and recreation’ or ‘industrial’ purpose group (purpose group 4, 5 or 6).
b. They have a storey area of 900m2 or more.
c. They have a storey height of 7.5m or more above fire and rescue service vehicle access level.