Section 17: Access to buildings for firefighting personnel Provision of firefighting shafts
Provision of firefighting shafts
17.2
A building with a storey more than 18m above the fire and rescue service vehicle access level should have one or more firefighting shafts containing a firefighting lift. The number and location of firefighting shafts should comply with paragraphs 17.4 to 17.7. Firefighting shafts are not required to serve a basement that is not large or deep enough to need one (see paragraph 17.3 and Diagram 17.2).
17.3
A building with basement storeys should have firefighting shafts in accordance with the following.
The building’s height and size determine whether firefighting shafts also serve upper storeys.
17.4
Firefighting shafts should serve all storeys through which they pass.
17.5
A minimum of two firefighting shafts should be provided to buildings with a storey that has both of the following.
17.6
At least two firefighting shafts, which do not need to include firefighting lifts, should be provided if buildings meet all of the following.
Diagram 17.2 Provision of firefighting shafts