Section 17: Access to buildings for firefighting personnel Provision of firefighting shafts

Provision of firefighting shafts

17.2

A building with a storey more than 18m above the fire and rescue service vehicle access level should have one or more firefighting shafts containing a firefighting lift. The number and location of firefighting shafts should comply with paragraphs 17.4 to 17.7. Firefighting shafts are not required to serve a basement that is not large or deep enough to need one (see paragraph 17.3 and Diagram 17.2).

17.3

A building with basement storeys should have firefighting shafts in accordance with the following.

a. There is a basement more than 10m below the fire and rescue service vehicle access level. The firefighting shafts should contain firefighting lifts.
b. There are two or more basement storeys, each with a minimum area of 900m2. The firefighting shafts do not need to include firefighting lifts.

The building’s height and size determine whether firefighting shafts also serve upper storeys.

17.4

Firefighting shafts should serve all storeys through which they pass.

17.5

A minimum of two firefighting shafts should be provided to buildings with a storey that has both of the following.

a. A floor area of 900m2 or more.
b. A floor level 18m or more above the fire and rescue service vehicle access level.

17.6

At least two firefighting shafts, which do not need to include firefighting lifts, should be provided if buildings meet all of the following.

a. They are in the ‘shop and commercial’, ‘assembly and recreation’ or ‘industrial’ purpose group (purpose group 4, 5 or 6).
b. They have a storey area of 900m2 or more.
c. They have a storey height of 7.5m or more above fire and rescue service vehicle access level.

Diagram 17.2 Provision of firefighting shafts

Diagram 17.2 Provision of firefighting shafts. Wording on the drawing: See para 17.2; Buildings in which firefighting shafts should be provided,; showing which storeys need to be served; a. Any building b. Any building c. ‘Shop and d. Any building commercial’, The upper storeys The basement The basement ‘assembly and in any building storeys in any storeys in any recreation’ and with a storey more building with a building with two ‘industrial’ than 18m above basement more or more buildings (purpose fire service vehicle than 10m below basements each groups 4, 5 and 6) access level fire service vehicle exceeding 900m² access level; The upper storeys in purpose groups 4, 5 and 6 buildings with a storey of 900m2 or more which is more than 7.5m above fire service vehicle access level; > 18m; Fire service vehicle; > 7.5m; access; level; > 10m; Two or more basement storeys each exceeding 900m²; NOTES:; 1. Height excludes any top storey(s) consisting exclusively of plant rooms.; Extent of firefighting; Extent of firefighting; stair lift 2. Firefighting shafts should serve all floors through which they pass.
Diagram 17.2 Provision of firefighting shafts