Access lobbies and corridors 3.34

3.34

In the following situations, protected lobbies or protected corridors should be provided at all storeys above ground, except the top storey.

a. If the stair is the only one serving a building or part of a building that has more than one storey above or below the ground storey.
b. If the stair serves any storey at a height of 18m or more above ground level.
c. If the building is designed for phased evacuation.
d. If the stair is a firefighting stair.
e. If the option in paragraph 3.15b has been used so as not to discount one stair when calculating stair widths.

As an alternative to (a) to (c), a smoke control system as described in paragraph 3.15a may be used.