Section 3: Design for vertical escape Design and protection of escape stairs

Design and protection of escape stairs

Enclosure of escape stairs

3.23

Every internal escape stair should be a protected stairway (within a fire resisting enclosure). If it is also a protected shaft (i.e. it passes from one compartment to another) or firefighting shaft, additional guidance in Sections 8 and 17 applies.

There is one exception: an unprotected stair (e.g. an accommodation stair) may form part of an internal route to a storey exit or final exit, provided that the distance of travel and the number of people involved are very limited. For example, small premises (Section 4) and raised storage areas (see paragraphs 7.6 and 7.7).

Construction of escape stairs

3.24

The flights and landings of escape stairs should be constructed of materials achieving class A2-s3, d2 or better in all of the following situations.

a. If the escape stair is the only stair serving the building or part of the building, unless the building has two or three storeys and is an office building.
b. If the escape stair is within a basement storey.
c. If the escape stair serves any storey that has a floor level more than 18m above ground or access level.
d. If the escape stair is external, except where the stair connects the ground floor or ground level with a floor or flat roof a maximum of 6m above or below ground level.
e. If the escape stair is a firefighting stair.

Materials achieving class B-s3, d2 or worse may be added to the top horizontal surface, except on firefighting stairs.

3.25

Further guidance on firefighting stairs is given in Section 17. Dimensional constraints on the design of stairs are given in Approved Document K.

Single steps

3.26

Single steps on escape routes should be prominently marked. A single step on the line of a doorway is acceptable, subject to paragraph 5.22.

Helical stairs and spiral stairs

3.27

Helical stairs and spiral stairs may form part of an escape route provided they are designed in accordance with BS 5395-2. If they are intended to serve members of the public, stairs should be type E (public) stairs.

Fixed ladders

3.28

Fixed ladders should not be provided as a means of escape for members of the public. They should only be provided where a conventional stair is impractical, such as for access to plant rooms which are not normally occupied.

External walls adjacent to protected stairways

3.29

With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.3).

3.30

If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.

Diagram 3.3 External protection to protected stairways

Diagram 3.3 External protection to protected stairways. Wording on the drawing: See para 3.29; Configurations of stairs and external wall; Accommodation; Accommodation; Fire resisting construction 1800mm min. of adjacent building enclosure; Fire resisting construction of protected stairway; 1800mm min.; 1800mm min.; Stair; Stair; Non-fire resisting construction; Accommodation; Accommodation; Configuration A Configuration B
Diagram 3.3 External protection to protected stairways

External escape stairs

3.31

Where a storey or part of the building has more than one escape route available, some of the escape routes may be via an external escape stair, provided the following conditions are met.

a. There is at least one internal escape stair from every part of each storey (excluding plant areas).
b. In the case of an ‘assembly and recreation’ (purpose group 5) building, the route is not intended for use by the public.
c. In the case of a ‘residential (institutional)’ (purpose group 2(a)) building, the route serves only office or residential staff accommodation.

3.32

Any external escape stair should meet all of the following conditions (Diagram 3.4).

a. Doors to the stair should be fire resisting (minimum E 30) and be fitted with a self-closing device, except for a single exit door from the building to the top landing of a downward-leading external stair, provided it is the only door onto the landing.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm above and horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape route from the foot of the external escape stair.
d. Stairs more than 6m in height should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
e. Glazing in areas of fire resisting construction should be fixed shut and fire resisting, in terms of integrity but not insulation (minimum E 30).

3.33

Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraphs 2.31 and 2.32.

Diagram 3.4 Fire resistance of areas near to external stairs

Diagram 3.4 Fire resistance of areas near to external stairs. Wording on the drawing: See para 3.32; Example a.; No fire resistance required for door; Fire resisting window (minimum RE 30); 1100mm above top landing; 1800mm; Fd; 1800mm; 9m below stair; 1800mm; fights and; Fd Fire doorset (minimum E 30); landings; Fd; Ground level or a roof or podium served by an independent stairway; Fire resisting construction (minimum RE 30); Example b.; 1100mm above top; landing; Fd 1800mm; 1800mm; 9m; below stair; fights and; Ground level or a roof or podium served by an independent stairway; landings; Section A–A Section B–B; A; 1800mm; B B NOTE: See para 3.31 on the provision of external stairs. See para 3.32d for weather Plan protection provisions. A; 1800mm
Diagram 3.4 Fire resistance of areas near to external stairs

Access lobbies and corridors

3.34

In the following situations, protected lobbies or protected corridors should be provided at all storeys above ground, except the top storey.

a. If the stair is the only one serving a building or part of a building that has more than one storey above or below the ground storey.
b. If the stair serves any storey at a height of 18m or more above ground level.
c. If the building is designed for phased evacuation.
d. If the stair is a firefighting stair.
e. If the option in paragraph 3.15b has been used so as not to discount one stair when calculating stair widths.

As an alternative to (a) to (c), a smoke control system as described in paragraph 3.15a may be used.

3.35

A protected lobby should be provided between an escape stair and a place of special fire hazard to protect from the ingress of smoke. The lobby should have a minimum 0.4m2 of permanent ventilation, or be protected by a mechanical smoke control system.

Exits from protected stairways

3.36

Every protected stairway should lead to a final exit, either directly or via an exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves. The exit from a protected stairway should comply with paragraphs 5.20 to 5.24.

Separation of adjoining protected stairways

3.37

The construction separating two adjacent protected stairways (or exit passageways) leading to different final exits should be imperforate.

Use of space within protected stairways

3.38

A protected stairway may only include any of the following.

a. Sanitary accommodation or washrooms, as long as the accommodation is not used as a cloakroom. A gas water heater or sanitary towel incinerator may be installed in the accommodation, but no other gas appliance.
b. If the protected stairway is not a firefighting stair: a lift well.
c. If the protected stairway is not the only stair serving the building or part of the building: a reception desk or enquiry office area at ground or access level. The reception or enquiry office area should have a maximum area of 10m2.
d. If the protected stairway is not the only stair serving the building or part of the building: cupboards enclosed with fire resisting construction.

Gas service and installation pipes in protected stairways

3.39

Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.

Basement stairs

3.40

An escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.

3.41

Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.

View this page on RegsUK