5.8

Electrically powered locks should return to the unlocked position in all of the following situations.

a. If the fire detection and alarm system operates.
b. If there is loss of power or system error.
c. If the security mechanism override is activated.

Security mechanism overrides for electrically powered locks should be a Type A call point as described in BS 7273-4. The call point should be positioned on the side approached by people escaping. If the door provides escape in either direction, a call point should be installed on both sides of the door.