Doors on escape routes Door fastenings
Door fastenings
5.7
In general, doors on escape routes (whether or not the doors are fire doorsets) should be either of the following.
Doors may be fitted with hardware to allow them to be locked when rooms are empty.
In places such as hotel bedrooms, locks may be fitted that are key operated from the outside and manually opened from the inside.
If a secure door is operated by code or combination keypad, swipe or proximity card, biometric data, etc., a security mechanism override should be possible from the side approached by people escaping.
5.8
Electrically powered locks should return to the unlocked position in all of the following situations.
Security mechanism overrides for electrically powered locks should be a Type A call point as described in BS 7273-4. The call point should be positioned on the side approached by people escaping. If the door provides escape in either direction, a call point should be installed on both sides of the door.
5.9
In places of assembly and shop and commercial buildings (purpose groups 4 and 5), doors on escape routes from rooms with more than 60 people should be either of the following.
In non-residential buildings (purpose groups 3 to 7), some final exit doors feature security locks that are used only when the building is empty. Such locks may be appropriate, but management procedures must emphasise their safe use.
5.10
Guidance on door closing and ‘hold open’ devices for fire doorsets is set out in Appendix C.