Maximum dimensions of cavities 9.10
9.10
Table 9.1 does not apply to any of the following cavities.
a. A cavity in a wall that is fire resisting only because it is loadbearing.
b. A cavity in a wall that meets the conditions of Diagram 9.2.
c. A floor or roof cavity above a fire resisting ceiling (Diagram 9.3) that extends throughout the building or compartment to a maximum of 30m.
d. In a building not put to residential or institutional use, a cavity that does not contain materials achieving class B-s3, d2 or worse and is formed either:
i. behind the external skin of an external cladding system with a masonry or concrete inner leaf a minimum of 75mm thick
ii. by overcladding an existing masonry (or concrete) external wall or an existing concrete roof.
e. A cavity that meets the conditions of paragraph 9.8.
f. A cavity below a floor next to the ground or next to oversite concrete, if either:
i. the cavity is less than 1000mm in height
ii. the cavity is not normally accessible by people, unless there are openings in the floor such that it is possible for materials to accumulate in the cavity (in which case cavity barriers should be provided and access should be provided to the cavity for cleaning).