Section 9: Cavities
Section 9: Cavities
9.1
Cavities in the construction of a building provide a ready route for the spread of smoke and flame, which can present a greater danger as any spread is concealed. For the purpose of this document, a cavity is considered to be any concealed space.
Diagram 9.1 Provisions for cavity barriers

Provision of cavity barriers
9.2
To reduce the potential for fire spread, cavity barriers should be provided for both of the following.
See Diagram 9.1. Cavity barriers should not be confused with fire-stopping details (Section 10).
Pathways around fire-separating elements
Junctions and edges of cavities
9.3
Cavity barriers should be provided at all of the following locations.
This does not apply where a wall meets the conditions of Diagram 9.2.
9.4
It is not appropriate to complete a line of compartment walls by fitting cavity barriers above them. The compartment wall should extend to the underside of the floor or roof above.
Protected escape routes
9.5
If the fire resisting construction of a protected escape route is either of the following.
Then the cavity above or below the fire resisting construction should be either of the following.
Cavities affecting alternative escape routes
9.6
In divided corridors, cavity barriers may be needed to prevent alternative escape routes being affected by fire and/or smoke (see paragraph 2.27 and Diagram 2.9).
Separation of bedrooms in ‘residential (institutional)’ and ‘residential (other)’ buildings
9.7
Where a cavity exists above or below a partition between bedrooms because the enclosure is not carried to full storey height or to the underside of the roof covering, the guidance in paragraph 9.5 should be followed.
Double-skinned corrugated or profiled roof sheeting
9.8
Cavity barriers are not required between double-skinned corrugated or profiled insulated roof sheeting if the sheeting complies with all of the following.
Diagram 9.2 Cavity walls excluded from provisions for cavity barriers

Diagram 9.3 Fire resisting ceiling below cavity

Diagram 9.4 Provisions for cavity barriers in double-skinned insulated roof sheeting

Extensive cavities
Maximum dimensions of cavities
9.9
Cavity barriers should be used to divide any cavity (including roof spaces). Table 9.1 sets out maximum dimensions for undivided cavities.
Table 9.1 Maximum dimensions of cavities in buildings other than dwellings (purpose groups 2 to 7)
| Location of cavity | Class of surface/product exposed in cavity (excluding the surface of any pipe, cable or conduit, or any insulation to any pipe) | Maximum dimension in any direction (m) |
|---|---|---|
| Between roof and a ceiling | Any | 20 |
| Any other cavity | Class C-s3, d2 or better | 20 |
| Worse than Class C-s3, d2 | 10 |
9.10
Table 9.1 does not apply to any of the following cavities.
9.11
If a single room with a ceiling cavity or underfloor cavity exceeds the dimensions in Table 9.1, cavity barriers need only be provided on the line of the enclosing walls/partitions of that room, if both of the following apply.
9.12
If the cavity is over an undivided area that exceeds 40m in any direction, there is no limit to its size if all of the following conditions are met.
Construction and fixings for cavity barriers
9.13
Cavity barriers, tested from each side separately, should provide a minimum of both of the following:
They may be formed by a construction provided for another purpose if it achieves the same performance.
9.14
Cavity barriers in a stud wall or partition, or provided around openings, may be formed of any of the following.
These do not necessarily achieve the performance specified in paragraph 9.13.
NOTE: Cavity barriers provided around openings may be formed by the window or door frame if the frame is constructed of steel or timber of the minimum thickness in (a) or (b), as appropriate.
9.15
Cavity barriers should be tightly fitted to a rigid construction and mechanically fixed in position. If this is not possible (e.g. where a cavity barrier joins to slates, tiles, corrugated sheeting or similar materials) the junction should be fire-stopped.
9.16
Cavity barriers should be fixed so their performance is unlikely to be made ineffective by any of the following.
Openings in cavity barriers
9.17
Openings should be limited to the following.
9.18
If a cavity barrier is provided above or below a partition between bedrooms in ‘residential (institutional)’ and ‘residential (other)’ (purpose groups 2(a) and 2(b)) buildings, and the partition is not a fire resisting partition, then paragraph 9.17 does not apply. However, both of the following apply.
NOTE: For further guidance on openings in cavity barriers see Section 10.