Section 9: Cavities Extensive cavities

Extensive cavities

Maximum dimensions of cavities

9.9

Cavity barriers should be used to divide any cavity (including roof spaces). Table 9.1 sets out maximum dimensions for undivided cavities.

Table 9.1 Maximum dimensions of cavities in buildings other than dwellings (purpose groups 2 to 7)

Location of cavityClass of surface/product exposed in cavity (excluding the surface of any pipe, cable or conduit, or any insulation to any pipe)Maximum dimension in any direction (m)
Between roof and a ceilingAny20
Any other cavityClass C-s3, d2 or better20
Worse than Class C-s3, d210

9.10

Table 9.1 does not apply to any of the following cavities.

a. A cavity in a wall that is fire resisting only because it is loadbearing.
b. A cavity in a wall that meets the conditions of Diagram 9.2.
c. A floor or roof cavity above a fire resisting ceiling (Diagram 9.3) that extends throughout the building or compartment to a maximum of 30m.
d. In a building not put to residential or institutional use, a cavity that does not contain materials achieving class B-s3, d2 or worse and is formed either:
i. behind the external skin of an external cladding system with a masonry or concrete inner leaf a minimum of 75mm thick
ii. by overcladding an existing masonry (or concrete) external wall or an existing concrete roof.
e. A cavity that meets the conditions of paragraph 9.8.
f. A cavity below a floor next to the ground or next to oversite concrete, if either:
i. the cavity is less than 1000mm in height
ii. the cavity is not normally accessible by people, unless there are openings in the floor such that it is possible for materials to accumulate in the cavity (in which case cavity barriers should be provided and access should be provided to the cavity for cleaning).

9.11

If a single room with a ceiling cavity or underfloor cavity exceeds the dimensions in Table 9.1, cavity barriers need only be provided on the line of the enclosing walls/partitions of that room, if both of the following apply.

a. The cavity barriers are a maximum of 40m apart.
b. The surface of the material/product exposed in the cavity is class C-s3, d2 or better.

9.12

If the cavity is over an undivided area that exceeds 40m in any direction, there is no limit to its size if all of the following conditions are met.

a. Together, the room and cavity form a compartment separated from the rest of the building.
b. Both of the following apply.
i. The building is fitted with an automatic fire detection and alarm system that conforms to BS 5839-1.
ii. Detectors are only required in the cavity to satisfy BS 5839-1.
c. If the cavity is used as a plenum then the recommendations for recirculating air distribution systems in Section 32 of BS 9999 are followed.
d. Both of the following apply.
i. The exposed surface of the material/product used in the construction of the cavity is class B-s3, d2 or better.
ii. The supports and fixings in the cavity are class A1.
e. Any pipe insulation system should achieve class C-s3, d2 rating or better.
f. Any electrical wiring in the cavity is laid in metal trays or metal conduit.
g. Other than those in (d)–(f), any materials are class A2-s3, d2 rated or better.