Maximum dimensions of cavities 9.11
9.11
If a single room with a ceiling cavity or underfloor cavity exceeds the dimensions in Table 9.1, cavity barriers need only be provided on the line of the enclosing walls/partitions of that room, if both of the following apply.
a. The cavity barriers are a maximum of 40m apart.
b. The surface of the material/product exposed in the cavity is class C-s3, d2 or better.