Maximum dimensions of cavities 9.12

9.12

If the cavity is over an undivided area that exceeds 40m in any direction, there is no limit to its size if all of the following conditions are met.

a. Together, the room and cavity form a compartment separated from the rest of the building.
b. Both of the following apply.
i. The building is fitted with an automatic fire detection and alarm system that conforms to BS 5839-1.
ii. Detectors are only required in the cavity to satisfy BS 5839-1.
c. If the cavity is used as a plenum then the recommendations for recirculating air distribution systems in Section 32 of BS 9999 are followed.
d. Both of the following apply.
i. The exposed surface of the material/product used in the construction of the cavity is class B-s3, d2 or better.
ii. The supports and fixings in the cavity are class A1.
e. Any pipe insulation system should achieve class C-s3, d2 rating or better.
f. Any electrical wiring in the cavity is laid in metal trays or metal conduit.
g. Other than those in (d)–(f), any materials are class A2-s3, d2 rated or better.