Provision of compartmentation All purpose groups

All purpose groups

8.1

All of the following should be provided as compartment walls and compartment floors and should have, as a minimum, the fire resistance given in Appendix B, Table B1.

8.2

A wall common to two or more buildings should be a compartment wall.

8.3

Parts of a building occupied mainly for different purposes should be separated from one another by compartment walls and/or compartment floors. Compartmentation is not needed if one of the different purposes is ancillary to the other. See paragraphs 0.23 and 0.24.

8.4

Effective compartmentation relies on both of the following.

a. Fire resistance should be continuous at the join between elements forming a compartment.
b. Any openings between two compartments should not reduce the fire resistance.

8.5

The lowest floor in a building does not need to be a compartment floor.