Section 8: Compartmentation/sprinklers Provision of compartmentation

Provision of compartmentation

All purpose groups

8.1

All of the following should be provided as compartment walls and compartment floors and should have, as a minimum, the fire resistance given in Appendix B, Table B1.

8.2

A wall common to two or more buildings should be a compartment wall.

8.3

Parts of a building occupied mainly for different purposes should be separated from one another by compartment walls and/or compartment floors. Compartmentation is not needed if one of the different purposes is ancillary to the other. See paragraphs 0.23 and 0.24.

8.4

Effective compartmentation relies on both of the following.

a. Fire resistance should be continuous at the join between elements forming a compartment.
b. Any openings between two compartments should not reduce the fire resistance.

8.5

The lowest floor in a building does not need to be a compartment floor.

Protected shafts

8.6

Stairs and service shafts connecting compartments should be protected to restrict the spread of fire between the compartments. These are called protected shafts. Walls or floors surrounding a protected shaft are considered to be compartment walls or compartment floors.

Places of special fire hazard

8.7

Fire resisting construction enclosing these places should achieve minimum REI 30. These walls and floors are not compartment walls and compartment floors.

‘Residential (institutional)’ buildings including health care

8.8

All floors should be constructed as compartment floors.

8.9

Paragraphs 2.35 and 2.36 give guidance on the provisions for compartment walls in care homes that use progressive horizontal evacuation.

‘Residential (other)’ buildings

8.10

In ‘residential (other)’ (purpose group (2(b)) buildings, all floors should be compartment floors.

Non-residential buildings

8.11

In buildings in a non-residential purpose group (purpose groups 3 to 7), the following should be compartment walls and compartment floors.

a. Every wall needed to divide the building to observe the compartment size limits in Table 8.1 (Diagram 8.1a).
b. Every floor, if the building or separated part of the building (see paragraph 8.19) has a top storey that is more than 30m above ground level (Diagram 8.1b).
c. The floor of the ground storey, if the building has one or more basements (Diagram 8.1c), except in small premises (see paragraph 4.2).
d. The floor of every basement storey (except the lowest floor), if the building or separated part has a basement more than 10m below ground level (Diagram 8.1d).
e. If the building comprises ‘shop and commercial’, ‘industrial’ or ‘storage’ premises (purpose groups 4, 6, 7): every wall or floor dividing a building into separate occupancies (spaces used by different organisations, whether they fall within the same purpose group or not).
f. See also the provision in paragraph 5.46 for store rooms in shops to be separated from retail areas by fire resisting construction (minimum REI 30).

8.12

In two storey ‘shop and commercial’ or ‘industrial’ buildings (purpose groups 4 or 6), where the use of the upper storey is ancillary to the use of the ground storey, the ground storey may be treated as a single storey building for fire compartmentation purposes where all of the following apply.

a. The area of the upper storey does not exceed the lower of:
i. 20% of the area of the ground storey
ii. 500m2.
b. The upper storey is compartmented from the lower one.
c. The upper storey has a means of escape independent of the lower storey escape routes.

Every place of special fire hazard (see Appendix E) should be enclosed with fire resisting construction.

Buildings containing one or more atria

8.13

Detailed advice on atria in buildings is given in Annexes B and C of BS 9999. For the purposes of this document, BS 9999 applies only where the atrium breaches a compartment.

Diagram 8.1 Compartment floors: illustration of guidance in paragraph 8.11

Diagram 8.1 Compartment floors: illustration of guidance in paragraph 8.11. Wording on the drawing: See para 8.11; b. Compartmentation in buildings over 30m see paragraph 8.11b Compartment floor(s) or wall(s); a. Example of compartmentation in an unsprinklered assembly and recreation, shop, or commercial building see paragraph 8.11a; > 30m; Storey not exceeding; 2000m²; Storey not exceeding; Roof; 2000m²; 30m max.; Storey exceeding 2000m² divided by compartment wall; Compartment; wall; Storey exceeding 2000m² divided by compartment wall; Compartment; wall; None of the floors in this case would need to be compartment floors, but the two storeys exceeding 2000m² would need to be divided into compartments not more than 2000m² by compartment walls.; In a building with a top storey over 30m in height all storeys should be separated by compartment floors. For advice on the special conditions in atrium buildings see Annex B of BS 9999.; The compartment walls in example (a) do not need to be in one vertical plane.; d. Deep basement see paragraph 8.11d; c. Shallow basement see paragraph 8.11c; > 10m; 10m max.; Only the floor of the ground storey need be a compartment floor if the lower basement is at a depth of not more than 10m.; All basement storeys to be separated by compartment floors if any storey is at a depth of more than 10m.
Diagram 8.1 Compartment floors: illustration of guidance in paragraph 8.11

Table 8.1 Maximum dimensions of building or compartment (non-residential buildings)

Purpose group of building or partHeight of floor of top storey above ground level (m)Maximum floor area of any one storey in the building or any one storey in a compartment (m2)
Single storey buildingsMulti-storey buildings
OfficeNo limit(1) No limitNo limit
Assembly and recreation, shop and commercial:
a. Shops – without sprinkler system
No limit(1) 20002000
Shops – with sprinkler system(2) No limitNo limit4000
b. Elsewhere – without sprinkler system
No limit(1) No limit2000
Elsewhere – with sprinkler system(2) No limitNo limit4000
Industrial(3)
Without sprinkler system(1) Not more than 18No limit7000
More than 18N/A2000(4)
With sprinkler system(2) Not more than 18No limit14,000
More than 18N/A4000(4)
Height of floor of top storey above ground level (m)Maximum floor area (m2)Maximum height (m)(5) Maximum compartment volume (m3)
Single storey buildingsMulti-storey buildings
Storage(3) and other non-residential:
a. Car park for light vehicles
No limitNo limitNo limitNo limit
b. Any other building or part:
Without sprinkler system(1) Not more than 1820,0001820,000
More than 18N/AN/A4000(4)
With sprinkler system(2) Not more than 18No limitNo limit40,000
More than 188000(4)

NOTES:

This table recommends that where the maximum size limitations placed on a building without a sprinkler system are exceeded, a sprinkler system in accordance with Appendix E should be provided.

1. See Appendix B, Table B2 for sprinkler system height requirements.
2. ‘With sprinkler system’ means that the building is fitted throughout with an automatic sprinkler system in accordance with Appendix E.
3. In certain industrial and storage uses that are subject to other legislation, for example the storage of LPG and certain chemicals, additional limitations on floor area and/or additional sprinkler provisions might apply.
4. This reduced limit applies only to storeys that are a minimum of 18m above ground level. Below this height the higher limit applies.
5. Compartment height is measured from finished floor level to the underside of the roof or ceiling.