Section 8: Compartmentation/sprinklers Provision of compartmentation
Provision of compartmentation
All purpose groups
8.1
All of the following should be provided as compartment walls and compartment floors and should have, as a minimum, the fire resistance given in Appendix B, Table B1.
8.2
A wall common to two or more buildings should be a compartment wall.
8.3
Parts of a building occupied mainly for different purposes should be separated from one another by compartment walls and/or compartment floors. Compartmentation is not needed if one of the different purposes is ancillary to the other. See paragraphs 0.23 and 0.24.
8.4
Effective compartmentation relies on both of the following.
8.5
The lowest floor in a building does not need to be a compartment floor.
Protected shafts
8.6
Stairs and service shafts connecting compartments should be protected to restrict the spread of fire between the compartments. These are called protected shafts. Walls or floors surrounding a protected shaft are considered to be compartment walls or compartment floors.
Places of special fire hazard
8.7
Fire resisting construction enclosing these places should achieve minimum REI 30. These walls and floors are not compartment walls and compartment floors.
‘Residential (institutional)’ buildings including health care
8.8
All floors should be constructed as compartment floors.
8.9
Paragraphs 2.35 and 2.36 give guidance on the provisions for compartment walls in care homes that use progressive horizontal evacuation.
‘Residential (other)’ buildings
8.10
In ‘residential (other)’ (purpose group (2(b)) buildings, all floors should be compartment floors.
Non-residential buildings
8.11
In buildings in a non-residential purpose group (purpose groups 3 to 7), the following should be compartment walls and compartment floors.
8.12
In two storey ‘shop and commercial’ or ‘industrial’ buildings (purpose groups 4 or 6), where the use of the upper storey is ancillary to the use of the ground storey, the ground storey may be treated as a single storey building for fire compartmentation purposes where all of the following apply.
Every place of special fire hazard (see Appendix E) should be enclosed with fire resisting construction.
Buildings containing one or more atria
8.13
Detailed advice on atria in buildings is given in Annexes B and C of BS 9999. For the purposes of this document, BS 9999 applies only where the atrium breaches a compartment.
Diagram 8.1 Compartment floors: illustration of guidance in paragraph 8.11

Table 8.1 Maximum dimensions of building or compartment (non-residential buildings)
| Purpose group of building or part | Height of floor of top storey above ground level (m) | Maximum floor area of any one storey in the building or any one storey in a compartment (m2) | ||
|---|---|---|---|---|
| Single storey buildings | Multi-storey buildings | |||
| Office | No limit(1) | No limit | No limit | |
| Assembly and recreation, shop and commercial: | ||||
a. Shops – without sprinkler system | No limit(1) | 2000 | 2000 | |
| Shops – with sprinkler system(2) | No limit | No limit | 4000 | |
b. Elsewhere – without sprinkler system | No limit(1) | No limit | 2000 | |
| Elsewhere – with sprinkler system(2) | No limit | No limit | 4000 | |
| Industrial(3) | ||||
| Without sprinkler system(1) | Not more than 18 | No limit | 7000 | |
| More than 18 | N/A | 2000(4) | ||
| With sprinkler system(2) | Not more than 18 | No limit | 14,000 | |
| More than 18 | N/A | 4000(4) | ||
| Height of floor of top storey above ground level (m) | Maximum floor area (m2) | Maximum height (m)(5) | Maximum compartment volume (m3) | |
| Single storey buildings | Multi-storey buildings | |||
| Storage(3) and other non-residential: | ||||
a. Car park for light vehicles | No limit | No limit | No limit | No limit |
b. Any other building or part: | ||||
| Without sprinkler system(1) | Not more than 18 | 20,000 | 18 | 20,000 |
| More than 18 | N/A | N/A | 4000(4) | |
| With sprinkler system(2) | Not more than 18 | No limit | No limit | 40,000 |
| More than 18 | 8000(4) | |||
NOTES:
This table recommends that where the maximum size limitations placed on a building without a sprinkler system are exceeded, a sprinkler system in accordance with Appendix E should be provided.