Escape route design Alternative escape routes
Alternative escape routes
2.10
Alternative escape route should satisfy one of the following criteria.
a. They are in directions 45 degrees or more apart (Diagram 2.2).
b. They are in directions less than 45 degrees apart, but separated from each other by fire resisting construction.
Diagram 2.2 Alternative escape routes