Section 2: Design for horizontal escape Escape route design
Escape route design
Number of escape routes and exits
2.3
The number of escape routes and exits that should be provided depends on both of the following.
2.4
In multi-storey buildings, if more than one stair is needed for vertical escape, every part of each storey should have access to more than one stair. An area may be in a dead end provided the alternative stair is accessible.
2.5
In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5).
Single escape routes and exits
2.6
A single escape route is acceptable for either of the following.
2.7
In many cases, the beginning of a route will not have an alternative escape route (for example, a single exit from a room into a corridor where escape is possible in two directions). This is acceptable if both of the following apply.
Diagram 2.1 shows how to measure travel distances from a dead end in an open storey layout.
Diagram 2.1 Travel distance in dead-end condition

Table 2.1 Limitations on travel distance
| Maximum travel distance(1) where travel is possible in: | ||||
|---|---|---|---|---|
| Purpose group | Use of the premises or part of the premises | One direction only (m) | More than one direction (m) | |
| 2(a) | Residential (institutional) | 9 | 18 | |
| 2(b) | Residential (other): | |||
a. in bedrooms(2) | 9 | 18 | ||
b. in bedroom corridors | 9 | 35 | ||
c. elsewhere | 18 | 35 | ||
| 3 | Office | 18 | 45 | |
| 4 | Shop and commercial | 18 | 45 | |
| 5 | Assembly and recreation: | |||
a. buildings primarily for disabled people | 9 | 18 | ||
b. areas with seating in rows | 15 | 32 | ||
c. elsewhere | 18 | 45 | ||
| 6 | Industrial(3) | Normal hazard | 25 | 45 |
| Higher hazard | 12 | 25 | ||
| 7 | Storage and other non-residential(3) | Normal hazard | 25 | 45 |
| Higher hazard | 12 | 25 | ||
| 2–7 | Place of special fire hazard(4) | 9(5) | 18(5) | |
| 2–7 | Plant room or roof-top plant: | |||
a. distance within the room | 9 | 35 | ||
b. escape route not in open air (overall travel distance) | 18 | 45 | ||
c. escape route in open air (overall travel distance) | 60 | 100 | ||
NOTES:
Access control measures
2.8
Measures to restrict access to the building (or parts of it) should not adversely affect fire safety provisions. It may be reasonable to close some escape routes outside normal business hours, but measures should remain to safely evacuate people left inside the building (see paragraph 5.6).
Number of occupants and exits
2.9
The building design should be based on the number of occupants. If the number is not known, use the appropriate floor space factors (Appendix D).
Table 2.2 gives the minimum number of escape routes and exits from a room or storey for different numbers of occupants. This number is likely to be increased by the need to observe travel distances and other practical considerations.
The width of escape routes and exits is given in paragraph 2.18.
Table 2.2 Minimum number of escape routes and exits from a room, tier or storey
| Maximum number of people | Minimum number of escape routes/exits |
|---|---|
| 60 | 1 |
| 600 | 2 |
| More than 600 | 3 |
Alternative escape routes
2.10
Alternative escape route should satisfy one of the following criteria.
Diagram 2.2 Alternative escape routes

Inner rooms
2.11
An inner room is at risk if a fire starts in the access room (Diagram 2.3). Such an arrangement should only be accepted if all of the following conditions are satisfied.
Diagram 2.3 Inner room and access room

Planning of exits in a central core
2.12
Where a central core has more than one exit, storey exits should be remote from one another and no two exits should be approached from the same lift hall, common lobby or undivided corridor (Diagram 2.4).
Open spatial planning
2.13
Escape routes should not be within 4.5m of openings between floors, such as for an escalator, unless either of the following applies.
Diagram 2.4 Exits in a central core

Diagram 2.5 Open connections

Access to storey exits
2.14
Where a storey has more than one escape stair, it should be planned so that it is not necessary to pass through one stair to reach another. However, it would be acceptable to pass through one stair’s protected lobby to reach another stair.
Separation of circulation routes from protected stairways
2.15
Where they serve protected stairways that are part of primary circulation routes, self-closing fire doors should be fitted with an automatic release mechanism, to avoid them being rendered ineffective by misuse. Otherwise, the stair (and any associated exit passageway) should not form part of the primary circulation route between different parts of the building at the same level.
Storeys divided into different uses
2.16
If a storey contains areas for consuming food and/or drink, and where that is not the main use of the building, then both of the following apply.
Storeys divided into different occupancies
2.17
Where a storey is divided into areas of occupancy under separate ownership or tenancy, then both of the following apply.
Width of escape routes and exits
2.18
The width of escape routes and exits should meet the provisions in Table 2.3, as well as the guidance in Approved Document M.
2.19
If the maximum number of people likely to use the escape route and exit is not known, it should be calculated using the occupant number guidance in Appendix D.
2.20
Guidance on the spacing of fixed seating for auditoria is given in Annex D of BS 9999.
Table 2.3 Widths of escape routes and exits
| Maximum number of people | Minimum width (mm)(1)(2)(3) |
|---|---|
| 60 | 750(4) |
| 110 | 850 |
| 220 | 1050 |
| More than 220 | 5 per person(5) |
NOTES:
Calculating exit capacity
2.21
Where multiple storey exits are available, fire might prevent one from being used. Remaining exits need to be wide enough for all occupants, so when using Table 2.3, the largest exit should be discounted.
Stairs should be at least as wide as any storey exit leading onto them. While some stairs are not subject to discounting (paragraphs 3.14 and 3.15), because the stairs will be available for other floors, the storey exits onto them are.
2.22
To calculate how many people two or more available exits (after discounting) can accommodate, add together the maximum numbers of people that each exit width can accommodate.
For example, three exits each 850mm wide accommodate 3×110 = 330 people.
2.23
If a ground floor storey exit and a stair share a final exit (via a ground floor lobby), then the final exit should be wide enough to evacuate people at a maximum flow rate equal to or greater than from the storey exit and stair combined (Diagram 2.6).
This can be calculated using the following formula:
W = ((N/2.5) + (60S))/80
where:
W is the width of final exit in metres
N is the number of people served by ground floor storey exit
S is the stair width in metres.
If the number of people (N) entering the lobby from the ground storey is more than 60, then the distance from the foot of the stair or the storey exit to the final exit should be a minimum of 2m (see Diagram 2.6).
If that minimum distance cannot be achieved, the width of the final exit (W) should be at least the width of the stair plus the width of the storey exit.
Diagram 2.6 Merging flows at final exit

Worked example
A ground floor storey exit serving 250 people shares a common final exit with a 1.2m wide stair.
Required final exit width = ((250/2.5) + (1.2×60))/80 = 2.150m
Protected corridors
2.24
A corridor serving as part of the means of escape in any of the following circumstances should be a protected corridor.
Diagram 2.7 Recesses off corridors

Diagram 2.8 Extension of corridor beyond a protected stairway

Enclosure of corridors that are not protected corridors
2.25
If a corridor is used for a means of escape but is not a protected corridor, even though the enclosing partitions may have no fire resistance, both of the following should be met to inhibit the spread of smoke.
Open planning will not inhibit the spread of smoke, but occupants can become aware of a fire quickly.
Division of corridors
2.26
A corridor providing access to alternative escape route should be divided by fire doorsets fitted with a self-closing device (and associated screens) where both of the following apply.
The fire doorsets (including any screens) should be approximately mid-way between the two storey exits. They should safeguard the route from smoke, while considering the layout of the corridor and any adjacent fire risks.
2.27
For buildings other than dwellings (purpose groups 2 to 7): if a cavity exists above the enclosures to a corridor as described above (because the enclosures are not carried to full storey height or the underside of the roof covering at the top storey), the potential for smoke to bypass the enclosure should be restricted by one of the following methods.
Any door that could provide a path for smoke to bypass the division should be fitted with a selfclosing device (but need not necessarily be fire resisting).
Diagram 2.9 Division of corridors

2.28
Where dead ends of corridors exceeding 4.5m long provide access to a point from which alternative escape route are available, they should be separated by self-closing fire doorsets (together with any associated screens) from any part of the corridor that either:
Alternatively, the stairs and corridors may be protected by a pressurisation system complying with BS EN 12101-6.
Diagram 2.10 Dead-end corridors exceeding 4.5m long

Cavity barriers
2.29
Additional measures to safeguard means of escape from smoke are given in Section 10.
External escape routes
2.30
Where an external escape route is beside an external wall of the building, the external wall should be of fire resisting construction in both of the following zones.
This does not apply to external escape stairs (see paragraph 3.32).
Escape over flat roofs
2.31
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof if it does not serve a ‘residential (institutional)’ (purpose group 2(a)) building, or part of a building intended for use by members of the public.
2.32
Where an escape route over a flat roof is provided, the roof should comply with all of the following.