Section 2: Design for horizontal escape

Section 2: Design for horizontal escape

Introduction

2.1

Means of escape should be provided from any point on a storey to the storey exit, for all types of building. The general principle is that any person confronted by a fire within a building can turn away from it and escape safely.

2.2

For small shop, office, industrial, storage and other similar premises, the guidance on small premises (see section 4) may be followed instead of the provisions in this section, if they meet both of the following conditions.

a. No storey has an area more than 280m2.
b. There is a maximum of two storeys plus a basement storey.

Escape route design

Number of escape routes and exits

2.3

The number of escape routes and exits that should be provided depends on both of the following.

a. The number of occupants in the room, tier or storey.
b. The limits on travel distance to the nearest exit given in Table 2.1 (which apply only to the nearest exit; other exits may be further away).

2.4

In multi-storey buildings, if more than one stair is needed for vertical escape, every part of each storey should have access to more than one stair. An area may be in a dead end provided the alternative stair is accessible.

2.5

In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5).

Single escape routes and exits

2.6

A single escape route is acceptable for either of the following.

a. Parts of a floor from which a storey exit can be reached within the limit for travel distance in one direction shown in Table 2.1 (see also paragraph 2.8), provided the following apply.
i. For places of assembly and bars, no one room in this situation has more than 60 people.
ii. For ‘residential (institutional)’ buildings (purpose group 2(a)), no one room in this situation has more than 30 people. Occupant number calculations are described in Appendix D.
b. A storey with no more than 60 people, where the limits on travel distance in one direction only are satisfied (see Table 2.1).

2.7

In many cases, the beginning of a route will not have an alternative escape route (for example, a single exit from a room into a corridor where escape is possible in two directions). This is acceptable if both of the following apply.

a. The travel distance to the nearest storey exit is within the limits for routes where escape is possible in more than one direction (Table 2.1).
b. The travel distance for the ‘one direction only’ section of the route does not exceed the limit for travel distance where there is no alternative escape route (Table 2.1).

Diagram 2.1 shows how to measure travel distances from a dead end in an open storey layout.

Diagram 2.1 Travel distance in dead-end condition

Diagram 2.1 Travel distance in dead-end condition. Wording on the drawing: See para 2.7; D; Travel distance in a dead-end condition Exit should meet all of the following.; A 45° min.; a. Angle ABD should be at least 45 degrees.; Exit; b. Distance CBA or CBD (whichever is less) should be no more than the maximum travel distance given for alternative escape routes.; B; c. Distance CB should be no more than the maximum travel distance where there are no alternative escape routes.; C
Diagram 2.1 Travel distance in dead-end condition

Table 2.1 Limitations on travel distance

Maximum travel distance(1) where travel is possible in:
Purpose groupUse of the premises or part of the premisesOne direction only (m)More than one direction (m)
2(a)Residential (institutional)918
2(b)Residential (other):
a. in bedrooms(2)
918
b. in bedroom corridors
935
c. elsewhere
1835
3Office1845
4Shop and commercial1845
5Assembly and recreation:
a. buildings primarily for disabled people
918
b. areas with seating in rows
1532
c. elsewhere
1845
6Industrial(3) Normal hazard2545
Higher hazard1225
7Storage and other non-residential(3) Normal hazard2545
Higher hazard1225
2–7Place of special fire hazard(4) 9(5) 18(5)
2–7Plant room or roof-top plant:
a. distance within the room
935
b. escape route not in open air (overall travel distance)
1845
c. escape route in open air (overall travel distance)
60100

NOTES:

1. If the internal layout of partitions, fittings, etc. is not known, direct distances, rather than travel distances, should be assessed. The direct distance should be assumed to be two-thirds of the actual travel distance.
2. Maximum part of travel distance within the room. This limit applies within the bedroom and any associated dressing room, bathroom or sitting room, etc. The distance is measured to the door to the protected corridor that serves the room or suite. Sub-item (b) applies from that point along the bedroom corridor to a storey exit.
3. In industrial and storage buildings, the appropriate travel distance depends on the level of fire hazard associated with the processes and materials being used.
Higher hazard includes manufacturing, processing or storage of significant amounts of hazardous goods or materials, including any of the following.
• Any compressed, liquefied or dissolved gas.
• Any substance that becomes dangerous by interaction with either air or water.
• Any liquid substance with a flash point below 65°C, including whisky or other alcoholic liquor.
• Any corrosive substance.
• Any oxidising agent.
• Any substance liable to spontaneous combustion.
• Any substance that changes or decomposes readily, giving out heat when doing so.
• Any solid substance with a flash point less than 120°C.
• Any substance that is likely to spread fire by flowing from one part of a building to another.
4. Places of special fire hazard are listed in the definitions in Appendix A.
5. Maximum part of travel distance within the room/area. Travel distance outside the room/area should comply with the limits for the purpose group of the building or part.

Access control measures

2.8

Measures to restrict access to the building (or parts of it) should not adversely affect fire safety provisions. It may be reasonable to close some escape routes outside normal business hours, but measures should remain to safely evacuate people left inside the building (see paragraph 5.6).

Number of occupants and exits

2.9

The building design should be based on the number of occupants. If the number is not known, use the appropriate floor space factors (Appendix D).

Table 2.2 gives the minimum number of escape routes and exits from a room or storey for different numbers of occupants. This number is likely to be increased by the need to observe travel distances and other practical considerations.

The width of escape routes and exits is given in paragraph 2.18.

Table 2.2 Minimum number of escape routes and exits from a room, tier or storey

Maximum number of peopleMinimum number of escape routes/exits
601
6002
More than 6003

Alternative escape routes

2.10

Alternative escape route should satisfy one of the following criteria.

a. They are in directions 45 degrees or more apart (Diagram 2.2).
b. They are in directions less than 45 degrees apart, but separated from each other by fire resisting construction.

Diagram 2.2 Alternative escape routes

Diagram 2.2 Alternative escape routes. Wording on the drawing: See para 2.10; Alternative escape routes are available from C because angle ACB A is 45 degrees or more and therefore distance CA or CB (whichever is the less) should be no more than the maximum travel distance given for alternative escape routes.; B; E; > 45°; < 45°; Alternative escape routes are not available from D because angle ADB is less than 45 degrees (therefore see Diagram 2.1).; D C; There is also no alternative escape route from E.
Diagram 2.2 Alternative escape routes

Inner rooms

2.11

An inner room is at risk if a fire starts in the access room (Diagram 2.3). Such an arrangement should only be accepted if all of the following conditions are satisfied.

a. The occupant number of the inner room does not exceed:
i. 30 people for ‘residential (institutional)’ buildings (purpose group 2(a))
ii. 60 people for other purpose groups.
b. The inner room is not a bedroom.
c. The inner room is entered directly from the access room (but not via a corridor).
d. The escape route from the inner room does not pass through more than one access room.
e. The travel distance from any point in the inner room to the exits from the access room does not exceed the distances in Table 2.1.
f. The access room meets both of the following conditions.
i. It is not a place of special fire hazard.
ii. It is in the control of the same occupier.
g. One of the following arrangements is made.
i. The enclosures (walls or partitions) of the inner room stop a minimum of 500mm below the ceiling.
ii. The door or walls of the inner room contain a vision panel (minimum 0.1m2), so people can see if a fire starts in the access room.
iii. The access room is fitted with an automatic fire detection and alarm system to warn occupants of the inner room if a fire starts in the access room.

Diagram 2.3 Inner room and access room

Diagram 2.3 Inner room and access room. Wording on the drawing: See para 2.11; Arrangement A Arrangement B; Exit Exit; Access room; NOTES:; Room with Inner room; alternative; Arrangement A Needs no special provision.; exits; Arrangement B Should observe the inner room; provisions in paragraph 2.11.; Exit
Diagram 2.3 Inner room and access room

Planning of exits in a central core

2.12

Where a central core has more than one exit, storey exits should be remote from one another and no two exits should be approached from the same lift hall, common lobby or undivided corridor (Diagram 2.4).

Open spatial planning

2.13

Escape routes should not be within 4.5m of openings between floors, such as for an escalator, unless either of the following applies.

a. The direction of travel is away from the opening.
b. An alternative escape route does not pass within 4.5m of the open connection (Diagram 2.5).

Diagram 2.4 Exits in a central core

Diagram 2.4 Exits in a central core. Wording on the drawing: See para 2.12; A; A A; A; C Fda; NOTE: The doors at both ends of the area marked ‘S’ should be self-closing fire doorsets unless the area is sub-divided such that any fire in that area will not be able to prejudice both sections of corridor at the same time. If that area is a lift lobby, doors should be provided as shown in Figure 9 in BS 9999.; Fd; Fd; PS; L; A; L; Fd Fd; S; L; L Lift S Services, toilets, etc. Fd Self-closing E 20 Sa fire doorsets Possible alternative position for fire doorset Fda C Corridor o… which accommodation opens Protected stairway PS A Accommodation (e.g. oƒce space – indicative layout shown); L; PS; Fd; Fd; Fda C; A A; A
Diagram 2.4 Exits in a central core

Diagram 2.5 Open connections

Diagram 2.5 Open connections. Wording on the drawing: See para 2.13; C; Area within 4.5m of the opening Escape route; From A and B at least one direction of travel Exit is away from the opening. From C, where the initial direction of travel is towards the opening, one of the escape routes is not less than 4.5m from the opening.; 4.5m; Opening; A; B; Exit
Diagram 2.5 Open connections

Access to storey exits

2.14

Where a storey has more than one escape stair, it should be planned so that it is not necessary to pass through one stair to reach another. However, it would be acceptable to pass through one stair’s protected lobby to reach another stair.

Separation of circulation routes from protected stairways

2.15

Where they serve protected stairways that are part of primary circulation routes, self-closing fire doors should be fitted with an automatic release mechanism, to avoid them being rendered ineffective by misuse. Otherwise, the stair (and any associated exit passageway) should not form part of the primary circulation route between different parts of the building at the same level.

Storeys divided into different uses

2.16

If a storey contains areas for consuming food and/or drink, and where that is not the main use of the building, then both of the following apply.

a. A minimum of two escape routes should be provided from each area, except from inner rooms that meet the conditions in paragraph 2.11.
b. Those escape routes should lead directly to a storey exit without entering a kitchen or similar area of high fire hazard.

Storeys divided into different occupancies

2.17

Where a storey is divided into areas of occupancy under separate ownership or tenancy, then both of the following apply.

a. The means of escape from each occupancy should not pass through any other occupancy.
b. If a common corridor or circulation space is on the escape route, one of the following should apply.
i. It should be a protected corridor.
ii. A suitable automatic fire detection and alarm system should be installed throughout the storey.

Width of escape routes and exits

2.18

The width of escape routes and exits should meet the provisions in Table 2.3, as well as the guidance in Approved Document M.

2.19

If the maximum number of people likely to use the escape route and exit is not known, it should be calculated using the occupant number guidance in Appendix D.

2.20

Guidance on the spacing of fixed seating for auditoria is given in Annex D of BS 9999.

Table 2.3 Widths of escape routes and exits

Maximum number of peopleMinimum width (mm)(1)(2)(3)
60750(4)
110850
2201050
More than 2205 per person(5)

NOTES:

1. See Appendix D for methods of measurement.
2. Widths may need to be increased to meet guidance in Approved Document M.
3. Widths less than 1050mm should not be interpolated.
4. May be reduced to 530mm for gangways between fixed storage racking, other than in public areas of ‘shop and commercial’ (purpose group 4) buildings.
5. 5mm/person does not apply to an opening serving fewer than 220 people.

Calculating exit capacity

2.21

Where multiple storey exits are available, fire might prevent one from being used. Remaining exits need to be wide enough for all occupants, so when using Table 2.3, the largest exit should be discounted.

Stairs should be at least as wide as any storey exit leading onto them. While some stairs are not subject to discounting (paragraphs 3.14 and 3.15), because the stairs will be available for other floors, the storey exits onto them are.

2.22

To calculate how many people two or more available exits (after discounting) can accommodate, add together the maximum numbers of people that each exit width can accommodate.

For example, three exits each 850mm wide accommodate 3×110 = 330 people.

2.23

If a ground floor storey exit and a stair share a final exit (via a ground floor lobby), then the final exit should be wide enough to evacuate people at a maximum flow rate equal to or greater than from the storey exit and stair combined (Diagram 2.6).

This can be calculated using the following formula:

W = ((N/2.5) + (60S))/80

where:

W is the width of final exit in metres

N is the number of people served by ground floor storey exit

S is the stair width in metres.

If the number of people (N) entering the lobby from the ground storey is more than 60, then the distance from the foot of the stair or the storey exit to the final exit should be a minimum of 2m (see Diagram 2.6).

If that minimum distance cannot be achieved, the width of the final exit (W) should be at least the width of the stair plus the width of the storey exit.

Diagram 2.6 Merging flows at final exit

Diagram 2.6 Merging flows at final exit. Wording on the drawing: See para 2.23; Escape stair; Storey exit (N); S; Ground floor; D Minimum 2m, where ‘N’ is greater than 60 people N Number of people served by ground floor storey exit W Width of final exit in metres S Stair width in metres; lobby; D; D; W; Final exit
Diagram 2.6 Merging flows at final exit

Worked example

A ground floor storey exit serving 250 people shares a common final exit with a 1.2m wide stair.

Required final exit width = ((250/2.5) + (1.2×60))/80 = 2.150m

Protected corridors

2.24

A corridor serving as part of the means of escape in any of the following circumstances should be a protected corridor.

a. Every corridor that serves bedrooms.
b. Every dead end corridor (excluding recesses and extensions a maximum of 2m deep, as shown in Diagrams 2.7 and 2.8).
c. Any corridor shared by two or more occupancies (paragraph 2.17).

Diagram 2.7 Recesses off corridors

Diagram 2.7 Recesses off corridors. Wording on the drawing: See para 2.24; 2m max. 2m max.; 2m max.; Corridor
Diagram 2.7 Recesses off corridors

Diagram 2.8 Extension of corridor beyond a protected stairway

Diagram 2.8 Extension of corridor beyond a protected stairway. Wording on the drawing: See para 2.24; 2m max.; 2m max.; Protected stairway; Protected; stairway; Example 1 Example 2
Diagram 2.8 Extension of corridor beyond a protected stairway

Enclosure of corridors that are not protected corridors

2.25

If a corridor is used for a means of escape but is not a protected corridor, even though the enclosing partitions may have no fire resistance, both of the following should be met to inhibit the spread of smoke.

a. Partitions should continue to the soffit of the structural floor above, or to a suspended ceiling.
b. Openings into rooms from the corridor should be fitted with doors, which do not need to be fire doorsets.

Open planning will not inhibit the spread of smoke, but occupants can become aware of a fire quickly.

Division of corridors

2.26

A corridor providing access to alternative escape route should be divided by fire doorsets fitted with a self-closing device (and associated screens) where both of the following apply.

a. It is more than 12m long.
b. It connects two or more storey exits.

The fire doorsets (including any screens) should be approximately mid-way between the two storey exits. They should safeguard the route from smoke, while considering the layout of the corridor and any adjacent fire risks.

2.27

For buildings other than dwellings (purpose groups 2 to 7): if a cavity exists above the enclosures to a corridor as described above (because the enclosures are not carried to full storey height or the underside of the roof covering at the top storey), the potential for smoke to bypass the enclosure should be restricted by one of the following methods.

a. Method 1 – Fitting cavity barriers on the line of the enclosure(s) to and across the corridor (Diagram 2.9).
b. Method 2 – Dividing the storey using fire resisting construction that passes through the line of the division of the corridor (Diagram 2.9). Any cavity above this division should be fitted with cavity barriers on the line of division of the storey and the corridor.
c. Method 3 – Enclosing the cavity on the lower side by a fire resisting ceiling that extends throughout the building, compartment or separated part.

Any door that could provide a path for smoke to bypass the division should be fitted with a selfclosing device (but need not necessarily be fire resisting).

Diagram 2.9 Division of corridors

Diagram 2.9 Division of corridors. Wording on the drawing: See para 2.27; Method 1 Cavity above ceiling; Method 2 Cavity above ceiling; Cavity barrier; Corridor; Fire resisting construction; Corridor; Fire resisting sub-division; Fd Fire doorset; Fd Fd; Fd; Fd; Floor cavity; Floor cavity; Section A; Section B; Fire resisting construction; Cavity barrier to ceiling cavity; Cavity barrier to ceiling cavity above fire resisting sub-division; Fd; Fd; Cavity barriers on line of corridor enclosure to any cavity above; Fd; Fd; A A B; B; Fire resisting sub-division.; Any cavity above to have cavity barriers; Fd; Fd; NOTES: The sub-division should be carried to full storey For all methods, where the corridor is a protected height and includes sub-division of the escape route, cavity barriers may also be required in corridor. A cavity barrier may be used in any any floor cavity beneath the corridor enclosure ceiling cavity over the sub-division. (see paragraph 9.5).
Diagram 2.9 Division of corridors

2.28

Where dead ends of corridors exceeding 4.5m long provide access to a point from which alternative escape route are available, they should be separated by self-closing fire doorsets (together with any associated screens) from any part of the corridor that either:

a. Provides two directions of escape (Diagram 2.10a)
b. Continues past one storey exit to another (Diagram 2.10b).

Alternatively, the stairs and corridors may be protected by a pressurisation system complying with BS EN 12101-6.

Diagram 2.10 Dead-end corridors exceeding 4.5m long

Diagram 2.10 Dead-end corridors exceeding 4.5m long. Wording on the drawing: See para 2.28; a. ‘T’ junction with b. Continuation main corridor past stairway; Fd Fd; Fd Fd; Fd; Fd Fd Fd Fd Fd Fd; Fd; Fd Fd; Fd Fd; Fd Self-closing fire doorsets; Protected corridor
Diagram 2.10 Dead-end corridors exceeding 4.5m long

Cavity barriers

2.29

Additional measures to safeguard means of escape from smoke are given in Section 10.

External escape routes

2.30

Where an external escape route is beside an external wall of the building, the external wall should be of fire resisting construction in both of the following zones.

a. Within 1800mm of the escape route.
b. Up to 1100mm above the surface of the escape route.

This does not apply to external escape stairs (see paragraph 3.32).

Escape over flat roofs

2.31

Where a storey or part of a building has multiple escape routes available, one may be over a flat roof if it does not serve a ‘residential (institutional)’ (purpose group 2(a)) building, or part of a building intended for use by members of the public.

2.32

Where an escape route over a flat roof is provided, the roof should comply with all of the following.

a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof forming the escape route and its supporting structure, together with any opening within 3m of the escape route, should be fire resisting (minimum REI 30).
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect from falling.

Residential care homes

General provisions

2.33

The choice of fire safety strategy depends on the way a building is designed, furnished, staffed and managed, and on the level of dependency of the residents.

2.34

In care homes for the elderly, some or all residents are likely to need help to evacuate. Buildings should generally be designed for progressive horizontal evacuation (PHE) in accordance with paragraphs 2.35 to 2.46.

For other care home types, the most appropriate of either a PHE or simultaneous evacuation strategy should be identified. The approach adopted in the design of a building must be recorded and communicated to the building management team, who can adopt procedures compatible with the building design.

Planning for progressive horizontal evacuation

2.35

The guidance below on PHE is for care homes where the provisions of the Firecode documents do not apply (see paragraph 0.10).

PHE requires areas used for the care of residents to be divided into protected areas by compartment walls and compartment floors. Protected areas provide a place of relative safety, from which further evacuation can be made if necessary.

2.36

Each storey used for the care of residents should be divided by compartment walls into at least three protected areas. All floors should be compartment floors.

2.37

Every protected area should have a minimum of two exits to adjoining protected areas. Maximum travel distances within a protected area should be both of the following.

a. To the exit to the adjoining protected area: as shown in Table 2.1.
b. From any point to a storey exit or a final exit: 64m.

2.38

A fire in one protected area should not prevent occupants of other areas from reaching a final exit (Diagram 2.11). Escape routes should not pass through ancillary accommodation listed in paragraph 2.44.

2.39

The number of residents’ beds in protected areas should be based on an assessment of both of the following.

a. The number of staff likely to be available.
b. The level of assistance that residents may require.

The maximum number of residents’ beds in one protected area should not exceed 10, but may need to be lower depending on the assessment.

2.40

A protected area used for horizontal evacuation from an adjoining protected area should have a floor area able to accommodate its own occupants plus those from the largest adjoining protected area.

Diagram 2.11 Progressive horizontal evacuation in care homes

Diagram 2.11 Progressive horizontal evacuation in care homes. Wording on the drawing: See para 2.38; Escape route to adjacent compartment, storey exit or final exit Compartment wall; Fire doorset in compartment wall; NOTE: Bedrooms and all ancillary accommodation should be enclosed in fire resisting construction.; Exit; Exit
Diagram 2.11 Progressive horizontal evacuation in care homes

Fire detection and alarm

2.41

A fire detection and alarm system should be provided to L1 standard in accordance with BS 5839-1.

Bedrooms

2.42

Each bedroom in a care home should be enclosed in fire resisting construction (minimum REI 30) with fire resisting doors (minimum E 30). Every corridor serving bedrooms should be a protected corridor (see paragraph 2.24).

2.43

Bedrooms should not contain more than one single or double bed.

NOTE: It is not the intention to separate couples who happen to live in a care home by recommending that they sleep in separate bedrooms or beds.

Ancillary accommodation

2.44

Ancillary accommodation such as all of the following should be enclosed by fire resisting construction (minimum REI 30).

a. Chemical stores.
b. Cleaners’ rooms.
c. Clothes storage.
d. Day rooms.
e. Smoking rooms.
f. Disposal rooms.
g. Plant rooms.
h. Linen stores.
i. Kitchens.
j. Laundry rooms.
k. Staff changing and locker rooms.
l. Store rooms.

Door closing devices

2.45

If doors fitted with a self-closing device could present an obstacle to residents, the following hardware in accordance with BS EN 1155 is appropriate.

a. Bedrooms: free-swing door closers.
b. Circulation spaces: hold-open devices.

Sprinkler systems

2.46

Care homes should be fitted with a sprinkler system throughout the building in accordance with Appendix E.