Appendix B: Performance of materials, products and structures Application of the fire resistance standards in Table B2

Application of the fire resistance standards in Table B2

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Application of the fire resistance standards in Table B2 (2029 amendment).

B25

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B25 (2029 amendment).

The following guidance should be used when applying the fire resistance standards in Table B2.

a. If one element of structure supports or carries or gives stability to another, the fire resistance of the supporting element should be no less than the minimum period of fire resistance for the other element (whether that other element is loadbearing or not). In some circumstances, it may be reasonable to vary this principle, for example:
i. if the supporting structure is in the open air and is not likely to be affected by the fire in the building
ii. if the supporting structure is in a different compartment, with a fire-separating element (that has the higher standard of fire resistance) between the supporting and the separated structure
iii. if a plant room on the roof needs greater fire resistance than the elements of structure that support it.
b. If an element of structure forms part of more than one building or compartment, that element should be constructed to the standard of the higher of the relevant provisions.
c. If, due to the slope of the ground, one side of a basement is open at ground level (allowing smoke to vent and providing access for firefighting) for elements of structure in that storey it may be appropriate to adopt the standard of fire resistance that applies to above-ground structures.
d. Although most elements of structure in a single storey building may not need fire resistance, fire resistance is needed if one of the following applies to the element.
i. It is part of, or supports, an external wall, and there is provision in the guidance on requirement B4 to limit the extent of openings and other unprotected areas in the wall.
ii. It is part of, or supports, a compartment wall, including a wall that is common to two or more buildings.
iii. It supports a gallery.

B26

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B26 (2029 amendment).

For the purposes of this paragraph, the ground storey of a building that has one or more basement storeys and no upper storeys may be considered as a single storey building. The fire resistance of the basement storeys should be that specified for basements.

Table B3 Limitations on the use of uninsulated glazed elements on escape routes. These limitations do not apply to glazed elements that satisfy the relevant insulation criterion, see Table B1

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Table B3 Limitations on the use of uninsulated glazed elements on escape routes. These limitations do not apply to glazed elements that satisfy the relevant insulation criterion, see Table B1 (2029 amendment).

Position of glazed elementMaximum total glazed area in parts of a building with access to:
A single stairMore than one stair
WallsDoor leafWallsDoor leaf
Flats
1. Within the enclosures of a protected entrance hall or protected landing, or within fire resisting separation shown in Section 3, Diagram 3.4, of Approved Document B Volume 1.
Fixed fanlights onlyUnlimited above 1100mm from floorFixed fanlights onlyUnlimited above 1100mm from floor
Dwellinghouses
2. Within either:
a. the enclosures of a protected stairway
b. fire resisting separation shown in Diagram 2.2 of Approved Document B Volume 1.
Unlimited above 1100mm from floor or pitch of the stairUnlimitedUnlimited above 1100mm from floor or pitch of the stairUnlimited
3. Within fire resisting separation either:
a. shown in Diagram 2.4 of Approved Document B Volume 1
b. described in paragraph 2.16b of Approved Document B Volume 1.
Unlimited above 100mm from floorUnlimited above 100mm from floorUnlimited above 100mm from floorUnlimited above 100mm from floor
4. Existing window between an attached/ integral garage and the dwellinghouse.
UnlimitedNot applicableUnlimitedNot applicable
5. Adjacent to an external escape stair (see paragraph 2.17 and Diagram 2.7 of Approved Document B Volume 1) or roof escape route (see paragraph 2.13 of Approved Document B Volume 1).
UnlimitedUnlimitedUnlimitedUnlimited
General (except dwellinghouses)
6. Between residential/sleeping accommodation and a common escape route (corridor, lobby or stair).
NilNilNilNil
7. Between a protected stairway(1) and either:
a. the accommodation
b. a corridor that is not a protected corridor other than in item 6 above.
Nil25% of door areaUnlimited above 1100mm(2) 50% of door area
8. Between either:
a. a protected stairway(1) and a protected lobby or protected corridor
b. accommodation and a protected lobby other than in item 6 above.
Unlimited above 1100mm from floorUnlimited above 100mm from floorUnlimited above 100mm from floorUnlimited above 100mm from floor
9. Between the accommodation and a protected corridor that forms a dead end, other than in item 6 above.
Unlimited above 1100mm from floorUnlimited above 100mm from floorUnlimited above 1100mm from floorUnlimited above 100mm from floor
10. Between accommodation and any other corridor, or subdividing corridors, other than in item 6 above.
Not applicableNot applicableUnlimited above 100mm from floorUnlimited above 100mm from floor
11. Beside an external escape route.
Unlimited above 1100mm from floorUnlimited above 1100mm from floorUnlimited above 1100mm from floorUnlimited above 1100mm from floor
12. Beside an external escape stair (see paragraph 3.32 and Diagram 3.4) or roof escape route (see paragraph 2.32).
UnlimitedUnlimitedUnlimitedUnlimited

NOTES:

Items 1 and 8 apply also to single storey buildings.

Fire resisting glass should be marked with the name of the manufacturer and the name of the product.

Further guidance can be found in A Guide to Best Practice in the Specification and Use of Fire-resistant Glazed Systems published by the Glass and Glazing Federation.

1. If the protected stairway is also a protected shaft or a firefighting stair (see Section 17), there may be further restrictions on the use of glazed elements.
2. Measured vertically from the landing floor level or the stair pitch line.
3. The 100mm limit is intended to reduce the risk of fire spreading from a floor covering.