Section 15: Vehicle access Buildings not fitted with fire mains

Buildings not fitted with fire mains

15.1

For small buildings (up to 2000m2, with a top storey that is a maximum of 11m above ground level), vehicle access for a pump appliance should be provided to whichever is the less onerous of the following.

a. 15% of the perimeter.
b. Within 45m of every point of the footprint of the building (see Diagram 15.1).

15.2

For all other buildings, provide vehicle access in accordance with Table 15.1.

15.3

Every elevation to which vehicle access is provided should have a door, a minimum of 750mm wide, to give access into the building. The maximum distance between doors, or between a door and the end of the elevation, is 60m (e.g. a 150m elevation would need a minimum of two doors).

Table 15.1 Fire and rescue service vehicle access to buildings not fitted with fire mains

Total floor area(1) of building (m²)Height of floor of top storey above ground (m)(2) Provide vehicle access to:Type of appliance
Up to 2000Up to 11See paragraph 15.1Pump
Over 1115% of perimeterHigh reach
2000–8000Up to 1115% of perimeterPump
Over 1150% of perimeterHigh reach
8000–16,000Up to 1150% of perimeterPump
Over 1150% of perimeterHigh reach
16,000–24,000Up to 1175% of perimeterPump
Over 1175% of perimeterHigh reach
Over 24,000Up to 11100% of perimeterPump
Over 11100% of perimeterHigh reach

NOTES:

1. The sum of the area of all storeys in the building (excluding basements).
2. For storage buildings (purpose group 7(a)), measure height to mean roof level (see Appendix D).

Diagram 15.1 Example of building footprint and perimeter

Diagram 15.1 Example of building footprint and perimeter. Wording on the drawing: See para 15.1; C D; A B; E F; J I L K H G; N M; Plan of building AFGL where AL and FG are walls in common with other buildings.; If the dimensions of the building are such that Table 15.1 requires vehicle access, the green shaded area illustrates one possible example of 15% of the perimeter. Note: There should be a door into the building in this length (see paragraph 15.3).; The footprint of the building is the maximum aggregate plan perimeter found by the vertical projection of any overhanging storey onto a ground storey (i.e. ABCDEFGHMNKL).; If the building does not have walls in common with other buildings, the lengths AL and FG would be included in the perimeter.; The perimeter of the building for the purposes of Table 15.1 is the sum of the lengths of the two external walls, taking account of the footprint, i.e. (A to B to C to D to E to F) + (G to H to M to N to K to L).
Diagram 15.1 Example of building footprint and perimeter