Buildings not fitted with fire mains Table 15.1 Fire and rescue service vehicle access to buildings not fitted with fire mains
Table 15.1 Fire and rescue service vehicle access to buildings not fitted with fire mains
| Total floor area(1) of building (m²) | Height of floor of top storey above ground (m)(2) | Provide vehicle access to: | Type of appliance |
|---|---|---|---|
| Up to 2000 | Up to 11 | See paragraph 15.1 | Pump |
| Over 11 | 15% of perimeter | High reach | |
| 2000–8000 | Up to 11 | 15% of perimeter | Pump |
| Over 11 | 50% of perimeter | High reach | |
| 8000–16,000 | Up to 11 | 50% of perimeter | Pump |
| Over 11 | 50% of perimeter | High reach | |
| 16,000–24,000 | Up to 11 | 75% of perimeter | Pump |
| Over 11 | 75% of perimeter | High reach | |
| Over 24,000 | Up to 11 | 100% of perimeter | Pump |
| Over 11 | 100% of perimeter | High reach |
NOTES:
1. The sum of the area of all storeys in the building (excluding basements).
2. For storage buildings (purpose group 7(a)), measure height to mean roof level (see Appendix D).