Appendix C: Fire doorsets C9
C9
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C9 (2029 amendment).
Rolling shutters should be capable of manual opening and closing for firefighting purposes (see Section 17). Rolling shutters across a means of escape should only be released by a heat sensor, such as a fusible link or electric heat detector, in the immediate vicinity of the door.
Unless a shutter is also intended to partially descend as part of a boundary to a smoke reservoir, shutters across a means of escape should not be closed by smoke detectors or a fire alarm system.