Appendix C: Fire doorsets (2029 amendment) C9 (2029 amendment)
C9 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C9.
Rolling shutters should be capable of manual opening and closing for firefighting purposes (see Section 17). Rolling shutters across a means of escape should only be released by a heat sensor, such as a fusible link or electric heat detector, in the immediate vicinity of the door.
Unless a shutter is also intended to partially descend as part of a boundary to a smoke reservoir, shutters across a means of escape should not be closed by smoke detectors or a fire alarm system.