Unprotected areas and fire resistance Canopies

Canopies

13.13

Where both of the following apply, separation distances may be determined from the wall rather than from the edge of the canopy (Diagram 13.6).

a. The canopy is attached to the side of a building.
b. The edges of the canopy are a minimum of 2m from the relevant boundary.

Canopies that fall within class 6 or class 7 of Schedule 2 to the regulations (Exempt Buildings and Work) are exempt from the Building Regulations.

13.14

Space separation may be disregarded if a canopy is all of the following.

a. Free-standing.
b. Above a limited risk or controlled hazard, for example over petrol pumps.
c. A minimum of 1000mm from the relevant boundary.

Diagram 13.6 The effect of a canopy on separation distance

Diagram 13.6 The effect of a canopy on separation distance. Wording on the drawing: See para 13.13; Canopy arrangement; Loading bay arrangement; 2m min. Canopy; 2m min.; Relevant boundary; Relevant Loading platform boundary; Building line Distance to; Building line; Distance to; relevant boundary; relevant boundary; measured from; measured from; building line; building line; NOTE: Projections from the building line, such as a canopy or a loading platform, can be ignored when assessing separation distance. This does not apply where the canopy is enclosed by side walls.
Diagram 13.6 The effect of a canopy on separation distance