Section 13: Resisting fire spread from one building to another Unprotected areas and fire resistance
Unprotected areas and fire resistance
13.6
Parts of an external wall with less fire resistance than the appropriate amount given in Appendix B, Table B2, are called unprotected areas.
13.7
Where a fire resisting external wall has an external surface material that is worse than class B-s3, d2 and is more than 1mm thick, that part of the wall should be classified as an unprotected area equating to half its area (Diagram 13.4).
External walls on, and within 1000mm of, the relevant boundary
13.8
Unprotected areas should meet the conditions in Diagram 13.5 and the rest of the wall should be fire resisting from both sides.
External surface materials facing the boundary should be class B-s3, d2 or better.
External walls 1000mm or more from the relevant boundary
13.9
Unprotected area should not exceed the result given by one of the methods in paragraph 13.17, and the rest of the wall (if any) should be fire resisting but only from the inside of the building.
External walls of protected stairways
13.10
Exclude external walls of stairways in a protected shaft when assessing unprotected areas (see Diagram 3.3)
Diagram 13.4 Status of materials achieving class B-s3, d2 or worse as unprotected area

Small unprotected areas
13.11
In an otherwise protected wall, small unprotected areas may be ignored where they meet the conditions in Diagram 13.5.
Diagram 13.5 Small unprotected areas that may be disregarded in assessing the separation distance from the boundary

Large uncompartmented buildings
13.12
For the purposes of assessing unprotected area, parts of walls of uncompartmented buildings that are more than 30m above mean ground level may be ignored.
Canopies
13.13
Where both of the following apply, separation distances may be determined from the wall rather than from the edge of the canopy (Diagram 13.6).
Canopies that fall within class 6 or class 7 of Schedule 2 to the regulations (Exempt Buildings and Work) are exempt from the Building Regulations.
13.14
Space separation may be disregarded if a canopy is all of the following.
Diagram 13.6 The effect of a canopy on separation distance

Roofs
13.15
Roofs with a pitch of more than 70 degrees to the horizontal should be assessed in accordance with this section. Vertical parts of a pitched roof, such as dormer windows, should be included, only if the slope of the roof exceeds 70 degrees.
It is a matter of judgement whether a continuous run of dormer windows that occupies most of a steeply pitched roof should be treated as a wall rather than a roof.
Portal frames
13.16
Portal frames are often used in single storey industrial and commercial buildings where there may be no need for fire resistance of the structure (requirement B3). However, where a portal framed building is near a relevant boundary, the external wall near the boundary may need fire resistance to restrict the spread of fire between buildings. It is generally accepted that a portal frame acts as a single structural element because of the moment-resisting connections used, especially at the column/rafter joints. Thus, in cases where the external wall of the building cannot be wholly unprotected, the rafter members of the frame, as well as the column members, may need to be fire protected. The design method for this is set out in SCI Publication P313.
NOTE: The recommendations in the SCI publication for designing the foundation to resist overturning do not need to be followed if the building is fitted with a sprinkler system in accordance with Appendix E.
NOTE: Normally, portal frames of reinforced concrete can support external walls requiring a similar degree of fire resistance without specific provision at the base to resist overturning.
NOTE: Existing buildings may have been designed to comply with all of the following guidance, which is also acceptable.