Section 15: Vehicle access Design of access routes and hardstandings

Design of access routes and hardstandings

15.7

Access routes and hardstandings should comply with the guidance in Table 15.2. Requirements can only apply to the site of the works.

It may not be reasonable to upgrade the route across a site to a small building. The building control body, in consultation with the fire and rescue service, should consider options from doing no work to upgrading certain features, such as sharp bends.

15.8

Where access to an elevation is provided in accordance with Table 15.1, the following requirements should be met, depending on the building height.

a. Buildings up to 11m, excluding small buildings (paragraph 15.1): pump appliance access should be provided adjacent to the building for the specified percentage of the total perimeter.
b. Buildings over 11m: access routes should comply with the guidance in Diagram 15.2.

15.9

Where access is provided for high reach appliances in accordance with Table 15.1, overhead obstructions (such as cables and branches) should be avoided in the zone shown in Diagram 15.2.

15.10

Dead-end access routes longer than 20m require turning facilities, as in Diagram 15.3. Turning facilities should comply with the guidance in Table 15.2.

Table 15.2 Typical fire and rescue service vehicle access route specification

Appliance typeMinimum width of road between kerbs (m)Minimum width of gateways (m)Minimum turning circle between kerbs (m)Minimum turning circle between walls (m)Minimum clearance height (m)Minimum carrying capacity (tonnes)
Pump3.73.116.819.23.712.5
High reach3.73.126.029.04.017.0

NOTES:

1. Fire appliances are not standardised. The building control body may, in consultation with the local fire and rescue service, use other dimensions.
2. The roadbase can be designed to 12.5 tonne capacity. Structures such as bridges should have the full 17-tonne capacity. The weight of high reach appliances is distributed over a number of axles, so infrequent use of a route designed to accommodate 12.5 tonnes should not cause damage.

Diagram 15.2 Relationship between building and hardstanding/access roads for high reach fire appliances

Diagram 15.2 Relationship between building and hardstanding/access roads for high reach fire appliances. Wording on the drawing: See paras 15.8 and 15.9; Overhead obstructions to be avoided in this zone; Face of building at ground level or vertical plane of projecting upper storey; a; b; c d; Obstruction; Hardstanding or access road; Type of appliance; Turntable Hydraulic ladder platform dimension (m) dimension (m); a. Maximum distance of near edge of hardstanding from building 4.9 2.0 b. Minimum width of hardstanding 5.0 5.5 c. Minimum distance of further edge of hardstanding from building 10.0 7.5 d. Minimum width of unobstructed space (for swing of appliance platform) N/A 2.2; NOTES:; 2. Fire appliances are not standardised. Some fire services have 1. Hardstanding for high reach appliances should be as appliances with a greater weight or di°erent size. level as possible and should have a maximum In consultation with the fire and rescue service, the building gradient of 1 in 12. control body should adopt the relevant dimensions and ground loading capacity.
Diagram 15.2 Relationship between building and hardstanding/access roads for high reach fire appliances

Diagram 15.3 Turning facilities

Diagram 15.3 Turning facilities. Wording on the drawing: See para 15.10; Fire and rescue service vehicles should not have to reverse more than 20m from the end of an access road.; Turning circle, hammerhead or other point at which vehicle can turn; Exit Building; 20m max.
Diagram 15.3 Turning facilities