Design of access routes and hardstandings Diagram 15.2 Relationship between building and hardstanding/access roads for high reach fire appliances

Diagram 15.2 Relationship between building and hardstanding/access roads for high reach fire appliances

Diagram 15.2 Relationship between building and hardstanding/access roads for high reach fire appliances. Wording on the drawing: See paras 15.8 and 15.9; Overhead obstructions to be avoided in this zone; Face of building at ground level or vertical plane of projecting upper storey; a; b; c d; Obstruction; Hardstanding or access road; Type of appliance; Turntable Hydraulic ladder platform dimension (m) dimension (m); a. Maximum distance of near edge of hardstanding from building 4.9 2.0 b. Minimum width of hardstanding 5.0 5.5 c. Minimum distance of further edge of hardstanding from building 10.0 7.5 d. Minimum width of unobstructed space (for swing of appliance platform) N/A 2.2; NOTES:; 2. Fire appliances are not standardised. Some fire services have 1. Hardstanding for high reach appliances should be as appliances with a greater weight or di°erent size. level as possible and should have a maximum In consultation with the fire and rescue service, the building gradient of 1 in 12. control body should adopt the relevant dimensions and ground loading capacity.